Parameter object, Class code, Services – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 239: Instances, Class attributes

EtherNet/IP Objects
C-5
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Parameter Object
Class Code
Important: This object is not supported when the adapter is used with a
PowerFlex 750-Series drive.
Services
Instances
The number of instances depends on the number of parameters in the DPI
drive. The adapter parameters are appended to the list of drive parameters.
The total number of parameters can be read in Instance 0, Attribute 2.
Class Attributes
Hexadecimal Decimal
0x0F
15
Service Code Implemented for:
Service Name
Class
Instance
0x01
Yes
Yes
Get_Attributes_All
0x05
Yes
No
Reset
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
Yes
Set_Attribute_Single
0x4B
No
Yes
Get_Enum_String
Instance
Description
0
Class Attributes
1
Drive Parameter 1 Attributes
…
…
n
Last Drive Parameter n Attributes
(1)
(1)
n represents the number of parameters in the drive.
n + 1
Adapter Parameter 1 Attributes
…
…
n + m
Last Adapter Parameter m Attributes
(2)
(2)
m represents the number of parameters in the adapter.
Attribute ID Access Rule Name
Data Type Description
1
Get
Revision
WORD
1
2
Get
Max Instance
WORD
Number of parameters
8
Get
Parameter Class Descriptor
WORD
0 = False, 1 = True
Bit 0 = Supports parameter instances
Bit 1 = Supports full attributes
Bit 2 = Must do NVS save command
Bit 3 = Parameters are stored in NVS
9
Get
Configuration Assembly Instance WORD
0
10
Set
Native Language
BYTE
0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch