Viewing adapter diagnostic items, Using the him to view adapter diagnostic items, Viewing adapter diagnostic items -4 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 204
7-4
Troubleshooting
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Viewing Adapter Diagnostic
Items
If you encounter unexpected communication problems, the adapter’s
diagnostic items may help you or Rockwell Automation personnel
troubleshoot the problem. Adapter diagnostic items can be viewed with any
of these drive configuration tools:
• LCD PowerFlex 7-Class HIM (Diagnostics/Device Items)
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 2.01 or later
• DriveExecutive software, version 3.01 or later
Using the HIM to View Adapter Diagnostic Items
Step
Example Screen
1. Access parameters in the adapter.
Using the PowerFlex 7-Class HIM to Access Parameters on
2. Press the
or
key to scroll to
Diagnostics.
3. Press the
(Enter) key to display the Diagnostics menu in the
adapter.
4. Repeat steps 2 and 3 to enter the
Device Items option.
5. Press the
or
key to scroll through the items.
Table 7.A Adapter Diagnostic Items
No. Name
Description
1
Common Logic Cmd
The present value of the Common Logic Command being
transmitted to the drive by this adapter.
2
Prod Logic Cmd
The present value of the Product Logic Command being transmitted
to the drive by this adapter from the controller.
3
Reference
The present value of the Reference being transmitted to the drive by
this adapter. Note that a 16-bit value will be sent as the Most
Significant Word of the 32-bit field.
4
Common Logic Sts
The present value of the Common Logic Status being received from
the drive by this adapter.
5
Prod Logic Sts
The present value of the Product Logic Status being received from
the drive by this adapter to the controller.
6
Feedback
The present value of the Feedback being received from the drive by
this adapter. Note that a 16-bit value will be sent as the Most
Significant Word of the 32-bit field.
7
Datalink A1 In
The present value of respective Datalink In being transmitted to the
drive by this adapter. (If not using a Datalink, this parameter should
have a value of zero.)
8
Datalink A2 In
9
Datalink B1 In
10
Datalink B2 In
11
Datalink C1 In
12
Datalink C2 In
13
Datalink D1 In
14
Datalink D2 In
Main Menu:
Diagnostics
Parameter
Device Select
Device Item #
3
Reference