Message structure for execute_dh – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 243
EtherNet/IP Objects
C-9
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Message Structure for Execute_DH+
The adapter supports the following PCCC command types:
For more information regarding PCCC commands, see DF1 Protocol and
Command Set Manual, publication 1770-6.5.16
.
Request
Response
Name
Data Type Description
Name
Data Type Description
DLink
UINT
Destination Link ID
DLink
UINT
Destination Link ID
DSta
USINT
Destination Station number
DSta
USINT
Destination Station number
DUser
USINT
Destination “User” number
DUser
USINT
Destination “User” number
SLink
UINT
Source Link ID
SLink
UINT
Source Link ID
SSta
USINT
Source Station number
SSta
USINT
Source Station number
SUser
USINT
Source User number
SUser
USINT
Source User number
CMD
USINT
Command byte
CMD
USINT
Command byte
STS
USINT
0
STS
USINT
Status byte
TNSW
UINT
Transport word
TNSW
UINT
Transport word. Same value as the request.
FNC
USINT
Function code; not used for all CMDs
EXT_STS USINT
Extended status; not used for all CMDs
PCCC_
params
ARRAY of
USINT
CMD/FNC specific parameters
PCCC_
results
ARRAY of
USINT
CMD/FNC specific result data
CMD
FNC
Description
0x06
0x03
Identify host and some status
0x0F
0x67
PLC-5 typed write
0x0F
0x68
PLC-5 typed read
0x0F
0x95
Encapsulate other protocol
0x0F
0xA2
SLC 500 protected typed read with 3 address fields
0x0F
0xAA
SLC 500 protected typed write with 3 address fields
0x0F
0xA1
SLC 500 protected typed read with 2 address fields
0x0F
0xA9
SLC 500 protected typed write with 2 address fields
0x0F
0x00
Word range read
0x0F
0x01
Word range write