Figure 4.9 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 74
4-28
Configuring the I/O
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Figure 4.9 PLC-5 Message Configuration Screens for the Logic Status,
Feedback, and Datalink Out
General Tab Box
Setting
This PLC-5
Communication Command
PLC-5 Typed Read. The controller type and command type for the controller to read data from the drive.
Data Table Address
(1)
N20:1. An unused controller data table address containing the data to be read from the drive.
Size in Elements
(2)
19. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
Port Number
2. Controller port to which the network is connected.
Target Device (data for adapter/drive)
Data Table Address
(3)
N41:0. Specific starting address of the source file in the drive.
MultiHop
Yes. Enables communication to allow network messaging to be routed to the adapter/drive. When ‘Yes’ is
selected, a MultiHop tab appears on the message configuration screen.
MultiHop Tab Box
Setting
To Address
10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, see
(2)
For details to determine element size for a specific drive, see
Understanding Controller Data Table Addresses on page 5-22
(3)
For N-File details, see