Viewing and clearing events, Viewing and clearing events -6 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 206

7-6
Troubleshooting
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Viewing and Clearing
Events
The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry is put into the
event queue. You can view the event queue with any of these drive
configuration tools:
• LCD PowerFlex 7-Class HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 2.01 or later
• DriveExecutive software, version 1.01 or later
The event queue can contain up to 32 entries. Eventually the event queue
will become full, since its contents are retained after adapter resets. At that
point, a new entry replaces the oldest entry. Only an event queue clear
operation or adapter power cycle will clear the event queue contents.
Resetting the adapter to defaults has no effect on the event queue.
45
46
47
48
Gateway Act 1
Gateway Act 2
Gateway Act 3
Gateway Act 4
Value of each byte in the adapter’s present gateway address. A
value of ‘0’ appears if the adapter does not currently have a gateway
address.
49
EN Rx Overruns
Number of receive buffer overruns reported by the Ethernet
hardware.
50
EN Rx Packets
Number of Ethernet packets that the adapter has received.
51
EN Rx Errors
Number of receive errors reported by the Ethernet hardware.
52
EN Tx Packets
Number of Ethernet packets that the adapter has sent.
53
EN Tx Errors
Number of transmit errors reported by the Ethernet hardware.
54
Last TCP Reset
Last reason that the adapter reset or rejected a TCP/IP connection.
55
Missed IO Pkts
Number of incoming I/O connection packets that the adapter did not
receive.
56
OPT Status
The operating status of optional I/O board in DPI External Comms
Kit. For the meanings of the individual bits, see
57
OPT RX Errors
Number of optional I/O board receive errors.
58
OPT FW Version
Firmware version of optional I/O board (in DPI External Comms Kit).
Table 7.A Adapter Diagnostic Items (Continued)
No. Name
Description
255.255.255.255
[Gateway Act 1]
[Gateway Act 2]
[Gateway Act 3]
[Gateway Act 4]