Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual
Page 208

7-8
Troubleshooting
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
11
Dup Port Flt
Another peripheral with the same port number is already in use.
12
Type 0 Login
The adapter has logged in for Type 0 control.
13
Type 0 Time Flt
The adapter has not received a Type 0 status message within the specified time.
14
DL Login
The adapter has logged into a Datalink.
15
DL Reject Flt
The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another
peripheral.
16
DL Time Flt
The adapter has not received a Datalink message within the specified time.
17
Reserved
Not used.
18
Control Disabled
The adapter has sent a ‘Soft Control Disable’ command to the drive.
19
Control Enabled
The adapter has sent a ‘Soft Control Enable’ command to the drive.
20
Message Timeout
A Client-Server message sent by the adapter was not completed within 1 sec.
21
Flt Cfg Error
One of the Flt Cfg xx parameters is set to a value greater than 65535 and the drive requires a 16-bit value.
22
App Updated
Startup sequence detected new application firmware.
23
EN Comm Flt
The adapter detected a communications fault on the network.
24
EN Sent Reset
The adapter received a reset from the network.
25
EN Close Flt
An I/O connection from the network to the adapter was closed.
26
EN Idle Flt
The adapter is receiving ‘idle’ packets from the network.
27
EN Open
An I/O connection from the network to the adapter has been opened.
28
EN Timeout Flt
An I/O connection from the network to the adapter has timed out.
29
PCCC IO Close
The device sending PCCC Control messages to the adapter has set the PCCC Control Timeout to zero.
30
PCCC IO Open
The adapter has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a
non-zero value).
31
PCCC IO Time Flt
The adapter has not received a PCCC Control message for longer than the PCCC Control Timeout.
32
Watchdog T/O Flt
The software detects a failure.
33
EEPROM Init
Startup sequence detected a blank EEPROM map revision.
34
Normal Startup
The adapter successfully started up.
35
Manual Reset
The adapter was reset by changing its Reset Module parameter.
36
EN Link Down
The Ethernet link was removed from the adapter.
37
EN Link Up
An Ethernet link is available for the adapter.
38
BOOTP Response
The adapter received a response to its BOOTP request.
39
Dup IP Addr
The adapter uses the same IP address as another device on the network.
40
Peer IO Open
The adapter received the first Peer I/O message.
41
Peer IO Time Flt
The adapter has not received a Peer I/O message for longer than the Peer I/O Timeout.
42
Email Failed
The adapter encountered an error attempting to send a requested e-mail message.
43
Msg Ctrl Open
The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing
control messages to be sent to the adapter.
44
Msg Ctrl Close
The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing
control messages to be sent to the adapter.
45
Msg Ctrl Timeout
The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.
46
OPT Open
The adapter began exchanging I/O data with the I/O option of the DPI External Comms Kit.
47
OPT Close
The adapter forced a fault condition on the I/O option of the DPI External Comms Kit.
48
OPT Timeout
Communication between the adapter and I/O option of the DPI External Comms Kit was disrupted.
Table 7.B Adapter Events (Continued)
Code
Event
Description