Direct mode: force mode – Festo Контроллеры двигателя SFC-LAC User Manual
Page 286

B. Supplementary information
B−66
Festo P.BE−GDCP−SFC−LACI−PB−E N en 0812NH
Direct mode: Force mode
Torque/Force Slope
PNU
550
ć
uint32
r
Description
Speed with which the force changes
CI
6087h
00h
uint32
r
Force Target Window
PNU
552
ć
ć
uint16
rw
Description
Target window of the force: This is the amount by which the actual force may
differ from the setpoint force in order to be interpreted as still being in the
target window.
The width of the window is thus twice the value transferred, with the target
position in the centre of the window.
The value is specified in
1
/
1000
of the nominal value (6076h / PNU 1036).
Value range: 0 ... 65535. Default: 100
CI
60F6h
0
3h
uint16
rw
Force Damping Time
PNU
553
ć
ć
uint16
rw
Description
Damping time of the force: If the actual force has been in the target window
this amount of time, the Motion Complete" bit will be set in the status word.
Value range: 0 ... 30000 ms. Default: 100 ms
CI
60F6h
0
4h
uint16
rw
Speed Limit
PNU
554
ć
ć
uint32
rw
Description
Maximum permitted velocity with active force control.
In this way you can ensure that, if force control is activated by mistake
(e.g.Ăwork item missing), the axis will not undergo uncontrolled acceleration
and move at high speed against a stop.
This parameter is taken into account in all control modes in which the position
controller is not active in the status Operation enabled".
CI
60F6h
0
2h
uint32
rw