C.1 CS I/O Communications Port

Pin configuration for the CR800 CS I/O port is listed in table CS I/O Pin
Description

(p. 527).

Table 119. CS I/O Pin Description

ABR: Abbreviation for the function name.
PIN: Pin number.
O: Signal Out of the CR800 to a peripheral.
I: Signal Into the CR800 from a peripheral.

PIN ABR I/O

Description

1

5 Vdc

O

5V: Sources 5 Vdc, used to power peripherals.

2 SG

Signal Ground: Provides a power return for pin 1 (5V),
and is used as a reference for voltage levels.

3 RING I

Ring: Raised by a peripheral to put the CR800 in the
telecommunications mode.

4 RXD I

Receive Data: Serial data transmitted by a peripheral are
received on pin 4.

5 ME O

Modem Enable: Raised when the CR800 determines that a
modem raised the ring line.

6 SDE O

Synchronous Device Enable: Used to address Synchronous
Devices (SDs), and can be used as an enable line for
printers.

7 CLK/HS I/O

Clock/Handshake: Used with the SDE and TXD lines to
address and transfer data to SDs. When not used as a
clock, pin 7 can be used as a handshake line (during
printer output, high enables, low disables).

8 +12

Vdc

9 TXD O

Transmit Data: Serial data are transmitted from the CR800
to peripherals on pin 9; logic-low marking (0V), logic-high
spacing (5V), standard-asynchronous ASCII, 8 data bits,
no parity, 1 start bit, 1 stop bit, 300, 1200, 2400, 4800,
9600, 19,200, 38,400, 115,200 baud (user selectable).

 

C.2 RS-232 Communications Port

C.2.1 Pin-Out

Pin configuration for the CR800 RS-232 nine-pin port is listed in table CR800 RS-
232 Pin-Out

(p. 528).

Information for using a null modem with RS-232 is given in

table Standard Null-Modem Cable or Adapter-Pin Connections

(p. 529).

The CR800 RS-232 port functions as either a DCE (data communication
equipment) or DTE (data terminal equipment) device. For RS-232 to function as a
DTE device, a null modem cable is required. The most common use of RS-232 is
as a connection to a computer DTE device. A standard DB9-to-DB9 cable can