Table 64. pulse-input channels and measurements – Campbell Scientific CR800 and CR850 Measurement and Control Systems User Manual

Page 306

background image

Section 8. Operation

306 

 

 

Table 68. Time Constants (τ)

Measurement

τ

Pulse channel, low-level ac mode

See table Filter Attenuation of

Frequency Signals

(p. 306)

footnote

Digital I/O, high-frequency mode

0.025

Digital I/O, switch-closure mode

0.025

 

Table 69. Filter Attenuation of Frequency Signals.

As shown for low-level ac inputs, increasing voltage is required at increasing frequencies to
overcome filter attenuation on pulse-input channels*.

ac mV (RMS)

Maximum Frequency

20

200

2000
5000

20

200

10,000
20,000

*8.5-ms time constant filter (19 Hz 3 dB frequency) for low-amplitude signals. 1-ms time
constant (159 Hz 3 dB frequency) for larger (> 0.7 V) amplitude signals.

 

Figure 96: Amplitude reduction of pulse-count waveform (before and after

1-µs time constant filter)