Campbell Scientific CR800 and CR850 Measurement and Control Systems User Manual
Page 289

Section 8. Operation
289
Table 59. Status Table Calibration Entries
Descriptions of Status Table Elements
Status Table
Element
Differential (Diff)
Single-Ended (SE)
Offset or Gain
±mV Input
Range
Integration
CalDiffOffset(16) Diff
Offset 25
50-Hz
Rejection
CalDiffOffset(17) Diff
Offset 7.5
50-Hz
Rejection
CalDiffOffset(18) Diff
Offset 2.5
50-Hz
Rejection
Table 60. Calibrate() Instruction Results
Descriptions of Array Elements
Array
Cal()
Element
Differential (Diff)
Single-Ended (SE)
Offset or Gain
±mV Input
Range
Integration
Typical Value
1 SE
Offset
5000 250
ms ±5
LSB
2 Diff
Offset
5000
250
ms ±5
LSB
3
Gain
5000
250 ms
-1.34 mV/LSB
4 SE
Offset
2500 250
ms ±5
LSB
5 Diff
Offset
2500
250
ms ±5
LSB
6
Gain
2500
250 ms
-0.67 mV/LSB
7 SE
Offset
250
250
ms ±5
LSB
8 Diff
Offset
250
250
ms ±5
LSB
9
Gain
250
250 ms
-0.067 mV/LSB
10 SE
Offset
25
250
ms ±5
LSB
11 Diff
Offset
25
250
ms ±5
LSB
12
Gain
25
250 ms
-0.0067 mV/LSB
13 SE
Offset
7.5
250
ms ±10
LSB
14 Diff
Offset
7.5
250
ms ±10
LSB
15
Gain
7.5
250 ms
-0.002 mV/LSB
16 SE
Offset
2.5
250
ms ±20
LSB
17 Diff
Offset
2.5
250
ms ±20
LSB
18
Gain
2.5
250 ms
-0.00067 mV/LSB
19
SE
Offset
5000
60-Hz Rejection
±5 LSB
20
Diff
Offset
5000
60-Hz Rejection
±5 LSB
21
Gain 5000
60-Hz
Rejection
-0.67
mV/LSB
22
SE
Offset
2500
60-Hz Rejection
±5 LSB
23
Diff
Offset
2500
60-Hz Rejection
±5 LSB
24
Gain 2500
60-Hz
Rejection
-0.34
mV/LSB
25
SE
Offset
250
60-Hz Rejection
±5 LSB
26
Diff
Offset
250
60-Hz Rejection
±5 LSB