Section 7. Installation

159

 

Public

Offset(3)

Alias

Offset(1) = Digits_Offset

Alias

Offset(2) = Temp_Offset

Alias

Offset(3) = BP_Offset

Public

LoadResult, CalMode

Public

AVWRC

Const

GageFactor = 0.01664

Const

Temp_K = -0.00517

BeginProg

'Load the calibration constants stored in the CAL file after a zero is performed

LoadResult = LoadFieldCal(False)

Scan

(1,Sec,1,0)

'AVW200(AVWRC,Com1,0,200,VW(1,1),1,1,1,1000,4000,1,_60Hz,1,0) '<

'instruction (commented out)

'Digits_Measured=(VW(1,1)^2)/1000 '<

Digits_Measured = 8746

'Temp_Measured=1/(1.4051E-3 + 2.369E-4 * LN(VW(1,6))+1.019E-7 * LN(VW(1,6)) ^3)-273.15

Temp_Measured = 21.4

'VoltSE(BP_Measured,1,mV2500,5,1,0,_60Hz,0.2,600) '<

'(commented out)

BP_Measured = 991

FieldCal

(4,Equation_Parameters(),3,0,Offset(),CalMode,0,1,1)


Pressure = (GageFactor * (Digits_Measured - Digits_Offset) + Temp_K * _
(Temp_Measured - Temp_Offset) - (BP_Measured - BP_Offset) * 0.014503)

NextScan

EndProg

7.8.1.5.4 Two-Point Slope and Offset (Option 2)

Case: A meter measures the volume of water flowing through a pipe. Multiplier
and offset are known to drift, so a two-point calibration is required periodically at
known flow rates. The following procedure adjusts multiplier and offset to correct
for meter drift as shown in the calibration report below. Note that the flow meter
outputs milliVolts inversely proportional to flow.

Table 24. Calibration Report for Flow Meter

Parameter

Parameter at Deployment Parameter at 7 Day Service

SignalmV output @ 30 L/s 300 mV

285 mV

SignalmV output @ 10 L/s 550 mV

522 mV

Multiplier

-0.0799 L/s/mV

-0.0841 L/s/mV

Offset

53.90 L

53.92 L