A.5.8 sdi-12, A.5.9 specific sensors – Campbell Scientific CR800 and CR850 Measurement and Control Systems User Manual
Page 465

Appendix A. CRBasic Programming Instructions
465
A.5.8 SDI-12
Read More! See SDI-12 Sensor Support
(p. 173).
SDI12Recorder
Retrieves the results from an SDI‐12 sensor.
Syntax
SDI12Recorder(Dest, SDIPort, SDIAddress, SDICommand,
Multiplier, Offset)
SDI12SensorSetup
Sets up the datalogger to act as an SDI‐12 sensor
SDI12SensorResponse
Holds the source of the data to send to the SDI‐12 recorder.
Syntax
SDI12SensorSetup(Repetitions, SDIPort, SDIAddress,
ResponseTime)
SDI12SensorResponse(SDI12Source)
A.5.9 Specific Sensors
ACPower
Measures real ac power and power‐quality parameters for single‐, split‐, and
three‐phase 'Y' configurations.
Syntax
ACPower(DestAC, ConfigAC, LineFrq, ChanV, VMult, MaxVrms,
ChanI, IMult, MaxIrms, Reps)
DANGER ac power can kill. User is responsible for ensuring connections to ac
power mains conforms to applicable electrical codes. Contact a Campbell
Scientific applications engineer for information on available isolation
transformers.
CS110
Measures electric field by means of a CS110 electric‐field meter.
Syntax
CS110(Dest, Leakage, Status, Integ, Mult, Offset)
CS110Shutter
Controls the shutter of a CS110 electric‐field meter.
Syntax
CS110Shutter(Status, Move)
CS616
Enables and measures a CS616 water content reflectometer.
Syntax
CS616(Dest, Reps, SEChan, Port, MeasPerPort, Mult, Offset)