beautypg.com

Table 20. logical expression examples – Campbell Scientific CR800 and CR850 Measurement and Control Systems User Manual

Page 149

background image

Section 7. Installation

149

 

Prc is the abbreviation of the name of the data process used. See table

Abbreviations of Names of Data Processes

(p. 149)

for a complete list of these

abbreviations. This is not needed for values from Status or Public tables.

Fieldname Index is the array element number in fields that are arrays

(optional).

Records Back is how far back into the table to go to get the value (optional).

If left blank, the most recent record is acquired.

Table 21. Abbreviations of Names of Data

Processes

Abbreviation Process

Name

Tot

Totalize

Avg

Average

Max

Maximum

Min

Minimum

SMM

Sample at Max or Min

Std

Standard Deviation

MMT

Moment

No abbreviation

Sample

Hst

Histogram

1

H4D

Histogram4D

FFT

FFT

Cov

Covariance

RFH

RainFlow Histogram

LCr

Level Crossing

WVc

WindVector

Med

Median

ETsz

ET

RSo

Solar Radiation (from ET)

TMx

Time of Max

TMn

Time of Min

1

Hst is reported in the form

Hst,20,1.0000e+00,0.0000e+00,1.0000e+01 where Hst denotes a
histogram, 20 = 20 bins, 1 = weighting factor, 0 = lower bound, 10 =
upper bound.

 

For instance, to access the number of watchdog errors, use the
status.watchdogerrors, where status is the table name, and watchdogerrors is
the field name.