Appendix B. Status Table and Settings

510 

 

 

Table 117. Status-Table Fields and Descriptions

Fieldname Description

Variable

Type

Default

Range

Edit?

Info

Type

FullMemReset

A value of 98765 written to
this location will initiate a
full memory reset. Full
memory reset will reinitialize
RAM disk, final storage,
PakBus memory, and return
parameters to defaults.

Integer 0

Enter
98765 to Reset

Config

DataTableName

Programmed name of data
table(s). Each table has its
own entry.

String array of number
of data tables

Prog

SkippedRecord10

Variable array that posts how
many records have been
skipped for a given table.
Each table has its own entry.

Integer array

0

0

Yes
Reset by
changing to 0

Error

DataRecordSize

Number of records in a table.
Each table has its own entry
in this array.

Integer array

SecsPerRecord

Output interval for a given
table. Each table has its own
entry in this array.

Integer array

DataFillDays

Time in days to fill a given
table. Each table has its own
entry.

Integer array

MeasureOps

Number of task-sequencer
opcodes required to do all
measurements in the system.
This value includes the
calibration opcodes (compile
time) and the background-
calibration (system), slow-
sequence opcodes. This is a
static value calculated at
compile time. Assumes all
measurement instructions
will run each scan.

Integer

Status

MeasureTime

Time (μs) required to make
the measurements in this
scan, including integration
and settling times. Processing
occurs concurrent with this
time so the sum of measure
time and process time is not
the time required in the scan
instruction. This is a static
value calculated at compile
time. Assumes all
measurement instructions
will run each scan.

Integer

Status