beautypg.com

6 testing applications, 1 configure hyperterminal – Campbell Scientific CR800 and CR850 Measurement and Control Systems User Manual

Page 212

background image

Section 7. Installation

212 

 

 

Scan

(5,Sec, 3, 0)

'Serial Out Code

'Transmits string "*27.435,56.789#" out COM1

SerialOpen

(Com1,9600,0,0,10000)

'Open a serial port

'Build the output string

SerialOutString = "*" & TempOut & "," & RhOut & "#"

'Output string via the serial port

SerialOut

(Com1,SerialOutString,"",0,100)

'Serial In Code

'Receives string "27.435,56.789" via COM2

'Uses * and # character as filters

SerialOpen

(Com2,9600,0,0,10000)

'Open a serial port

'Receive serial data as a string

'42 is ASCII code for "*", 35 is code for "#"

SerialInRecord

(Com2,SerialInString,42,0,35,"",01)

'Parse the serial string

SplitStr

(InStringSplit(),SerialInString,"",2,0)

NextScan

EndProg

 

7.8.8.6 Testing Applications

A common problem when developing a serial I/O application is the lack of an
immediately available serial device with which to develop and test programs.
Using HyperTerminal, a developer can simulate the output of a serial device or
capture serial input.

Note HyperTerminal is provided as a utility with Windows XP and earlier
versions of Windows. HyperTerminal is not provided with later versions of
Windows. HyperTerminal automatically converts binary data to ASCII on the
screen. Binary data can be captured, saved to a file, and then viewed with a
hexadecimal editor. Other terminal emulators are available from third-party
vendors that facilitate capture of binary or hexadecimal data.

7.8.8.6.1 Configure HyperTerminal

Create a HyperTerminal instance file by clicking Start | All Programs |
Accessories | Communications | HyperTerminal. The windows in the figures
HyperTerminal Connection Description

(p. 213)

through HyperTerminal ASCII

Setup

(p. 214)