A.10 custom keyboard and display menus – Campbell Scientific CR800 and CR850 Measurement and Control Systems User Manual
Page 486

Appendix A. CRBasic Programming Instructions
486
VoiceSpeak 
Defines the voice string that should be spoken by the voice modem. 
Syntax
VoiceSpeak("String" + Variable + "String"…, Precision)
A.10 Custom Keyboard and Display Menus
Read More! More information concerning use of the keyboard is found in 
sections Using the Keyboard Display
(p. 382)
and Read More! To implement
custom menus, see CRBasic Editor Help for the DisplayMenu() instruction.
CRBasic programming in the CR800 facilitates creation of custom menus for the 
external keyboard / display. 
Figure Custom Menu Example
(p. 70)
shows windows from a simple custom menu
named DataView. DataView appears as the main menu on the keyboard display. 
DataView has menu item Counter, and submenus PanelTemps, TCTemps and 
System Menu. Counter allows selection of one of four values. Each submenu 
displays two values from CR800 memory. PanelTemps shows the CR800 wiring-
panel temperature at each scan, and the one-minute sample of panel temperature. 
TCTemps displays two thermocouple temperatures.
.
Custom menus are constructed with the following syntax before the BeginProg 
instruction. 
DisplayMenu
("MenuName", AddToSystem)
MenuItem
("MenuItemName", Variable)
MenuPick
(Item1, Item2, Item3...)
DisplayValue
("MenuItemName", tablename.fieldname)
SubMenu
(MenuName)
MenuItem
("MenuItemName", Variable)
EndSubMenu
EndMenu
BeginProg
[program body]
EndProg
DisplayMenu / EndMenu 
Marks the beginning and ending of a custom menu.  
Syntax:
DisplayMenu("MenuName", AddToSystem) 
 [menu definition] 
EndMenu 
MenuItem 
Defines the name and associated measurement value for an item in a custom 
menu. 
Syntax:
MenuItem("MenuItemName", Variable)
DisplayLine 
Displays a full line of read‐only text in a custom menu. 
Syntax:
DisplayLine(Value)