Appendix B. Status Table and Settings

516 

 

 

Table 117. Status-Table Fields and Descriptions

Fieldname Description

Variable

Type

Default

Range

Edit?

Info

Type

CalDiffOffset

19

Calibration table of
differential offset values.
Each integration / range
combination has a
differential offset associated
with it. These numbers are
updated by the background
slow sequence if needed in
the program.

Integer array of 18

close to 0

Calib

1

The station name written to the header of data files by the datalogger support software (p. 76) is the

station name entered when the software was set up to communicate with the CR800. In contrast, the
station name set in the

Status

table (by typing it directly into the field, using the

StationName()

instruction, or using the

SetStatus()

instruction), can be sampled into a data table using data table

access syntax. See the Program Access to Data Tables (p. 148) section for more information.

2

PakBus Addresses 1 to 4094 are valid. Addresses >= 4000 are generally reserved for a PC by the

datalogger support software (p. 76).

3

Watchdog errors are automatically reset upon compiling a new program.

4

Replace the lithium battery if <2.7 Vdc. See Replacing the Internal Battery (p. 397) for replacement

directions.

5

The 12 Vdc low comparator has some variation, but typically triggers at about 9.0 Vdc. The

minimum-specified input voltage of 9.6 Vdc will not cause a 12-Vdc low condition, but a 12-Vdc low
condition will stop the program execution before the CR800 will give bad measurements on account of
low supply voltage.

6

A 1 indicates that the program was compiled due to the logger starting from a power-down condition.

A 0 indicates that the compile was caused by either a Program Send, a File Control transaction, or a
watchdog reset.

7

The VarOutOfBound error occurs when a program tries to write to an array variable outside of its

declared size. A programming error causes this, so it should not be ignored. When the datalogger
detects that a write outside of an array is being attempted, it does not perform the write and increments
the VarOutOfBound register. The compiler and pre-compiler can only catch things like reps too large
for an array, etc. If an array is used in a loop or expression, the pre-compiler does not (in most cases,
cannot) check to see if an array is accessed out of bounds (i.e. accessing an array with a variable index
such as arr(index) = arr(index-1), where index is a variable).

8

The background calibration runs automatically in a hidden SlowSequence scan. See the Self-

Calibration (p. 285) section.

9

If no user-entered SlowSequence scans are programmed, this variable is not listed in the table. If

multiple user-entered SlowSequence scans are programmed, this variable becomes an array with a
value for each scan.

10

The order of tables is the order in which they are declared.

12

Displays a large number until a SlowSequence scan runs.

13

Displays 0 until a SlowSequence scan runs.

14

Security can be changed via DeviceConfig, external keyboard / display, PakBusGraph,

Status

table, and SetSecurity() instruction. Shows -1 if the security code has not been given, or if it has been
deactivated.

15

In general, CommsActive is set to TRUE when receiving incoming characters, independent of the

protocol. It is set to FALSE after a 40 second timeout during which no incoming characters are
processed, or when the protocol is PakBus and the serial packet protocol on the COM port specifies off
line. Note, therefore, that for protocols other than PakBus that are serviced by the SerialIO()