background image

CH. 16 MAN0878-04-EN

August 12, 2009

Page 90 of 100

ECN # 979

3. User needs to confirm Load Clone as shown below:

XLt:

XLe:

Figure 16-8 – Load Clone Confirm Screen


4. After confirmation, all unit settings and register values will be loaded from Removable media to the

Battery backed RAM (Regardless of AutoLoad settings) and then OCS resets for the settings to take
effect.


NOTE: For security enabled files, Load clone asks for password validation before loading the application.

Load clone can also be triggered by setting %SR164.10 bit to “1” from Ladder program or graphics. Once
the operation is completed, this bit is made zero by the firmware. When Load clone operation is triggered
by this SR bit, it does not ask the user for confirmation for loading clone. The success / failure of the
operation is also not notified on screen to the user.

In case of failure of “Load Clone” operation, %SR164.12 bit is set to “1” by the firmware and never reset.