1 Specifications

Specifications

General Specifications

Required Power
(Steady State)

130 mA @ 24 VDC

Required Power
(Inrush)

30A for 1 ms @ 24 VDC

Primary Power
Range

10 – 30 VDC

Relative Humidity

5 to 95% Non-condensing

Clock Accuracy

+/- Seven Minutes/Month at 20C

Operating
Temperature

0

°C to +50°C

Terminal Type

Screw Type, 5 mm Removable

Weight

12 oz. (340.19 g)

CE

UL

See Compliance Table at :

http://www.heapg.com/Support/compli
ance.htm



2

Panel Cut-Out and Dimensions

Note: Max. panel thickness: 5 mm.

Refer to the User Manual for panel box information and a handy
checklist of requirements.

Note:
The tolerance to meet NEMA standards is

± 0.005” (0.1 mm).






































3

Ports / Connectors / Cables

Note: The case of the XLe is black, but for clarity, it is shown in a lighter gray color.







































XLE OCS Model:

HE-XE100 / HEXE220C100 / HEXE220C000

3.

62

2

[9

2m

m

]

3.622 [92mm]

001XLE002

Power Connector

Power Up:

Connect to Earth Ground.

Apply 10 - 30 VDC.

Screen lights up.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)

CAN Connector

Use the CAN Connector when

using CsCAN network.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)

To Remove Back Cover:

Unscrew 4 screws located on

the back of the unit and remove

back cover.

CAUTION: Do not over tighten

screws when replacing back

cover.

Memory Slot:

Uses Removable Memory for
data logging, screen captures,

program loading and recipes.

Horner Part No.: HE-MC1

Serial Communications:

MJ1: (RS-232 / RS-485) Use for

Cscape programming and

Application-Defined

Communications.

MJ2: (RS-232 / RS-485) Use for

Application-Defined

Communications.

MJ1

(RS-232 / RS-485)

MJ2

(RS-232 / RS-485)

Memory Slot

NET 1

(CsCAN)

Power

DIP

Switch

Note – Your keypad overlay

appearance may differ. Standard

US/EU overlays pictured here for

example.

This manual is related to the following products: