MAN0878-04-EN CH. 11

August 12, 2009

Page 55 of 100

ECN # 979

The first five System Diagnostics are critical. If any of them indicate a Fault condition, the XLe/XLt will not
enter or remain in Run mode, and the problem must be investigated and corrected.

System Ram:

Ok

= System RAM power-up self-test passed

Fault

= System RAM power-up self-test failed


System BIOS:

Ok

= System BIOS power-up self-test passed

Fault

= System BIOS power-up self-test failed


Firmware:

Ok

= Firmware power-up self-test passed

Fault

= Firmware power-up self-test failed


Logic Error:

Ok

= All executed ladder instructions are legal for loaded firmware

Fault

= A ladder instruction not supported by firmware was found


User Program:

Ok

= Ladder program and I/O configuration loaded successfully

Fault

= Ladder program or I/O configuration not loaded or load failed

The last nine System Diagnostics are informational. If any of them indicate a Warning condition, the
XLe/XLt can still enter and remain in Run mode, but the problem should be investigated and corrected.


User Graphics: Ok

=

Application

graphics

objects loaded successfully

Fault

= Application graphics objects not loaded or load failed

W-Dog Trips:

0

= Watchdog timer has not tripped since the last power-up

x

= Number of times watchdog timer has tripped


Net Errors:

0

= No CAN network bus-off errors have occurred

x

= Number of CAN network bus-off errors that have occurred


Network State:

Ok

= At least one other node was found on the CAN network

Warning

= No other nodes were found on the CAN network


Network ID:

Ok

= This node’s CAN Network ID is in the range 1 to 253

Warning

= This node’s CAN Network ID was out of range at power-up


Dup Net ID:

Ok

= This node’s Network ID is unique on the CAN network

Warning

= This node’s Network ID is duplicated in another node


Clock Error:

Ok

= Time and date have been set

Warning

= Time and date need to be set


I/O System:

Ok

= I/O configuration matches the installed I/O and COM modules

Warning

= I/O configuration needs updating to match installed modules


Battery:

Ok

= Backup battery operating properly

Warning

= Backup battery needs to be replaced



View I/O Slots

The View I/O Slots Sub-Menu displays two System Settings, both of which are not editable.

This manual is related to the following products: