beautypg.com

Horner APG XLt OCS HE-XT103-10 User Manual

Horner APG Sensors

background image

MAN0871-02

21

AUGUST

2007

PAGE

1

Specifications / Installation

HE-XT103-10









1 Specifications

HE-XT103-10 Specifications

Digital DC Inputs

XLT103-10

Digital DC

Outputs

XLT103-10

Inputs per Module

12 including 4 configurable

HSC inputs

Outputs per

Module

12 including 2 configurable

PWM outputs

Commons per

Module

1

Commons per

Module

1

Input Voltage

Range

12 VDC / 24 VDC

Output Type

Sourcing / 10 K Pull-Down

Absolute Max.

Voltage

35 VDC Max.

Absolute Max.

Voltage

28 VDC Max.

Input Impedance

10 k

Output

Protection

Short Circuit

Input Current

Positive

Logic

Negative Logic

Max. Output

Current per

point

0.5 A

Upper Threshold

0.8 mA

-1.6 mA

Max. Total

Current

4 A Continuous

Lower Threshold

0.3 mA

-2.1 mA

Max. Output

Supply Voltage

30 VDC

Max Upper

Threshold

8 VDC

Minimum Output

Supply Voltage

10 VDC

Min Lower

Threshold

3 VDC

Max. Voltage

Drop at Rated

Current

0.25 VDC

OFF to ON

Response

1 ms

Max. Inrush

Current

650 mA per channel

ON to OFF

Response

1 ms

Min. Load

None

HSC Max.

Switching Rate

10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width

2.5 kHz Quadrature

OFF to ON

Response

1 ms

Thermistor

Inputs, Medium

Resolution

XLT103-10

ON to OFF

Response

1 ms

Number of

Channels

2

Output

Characteristics

Current Sourcing (Pos logic)

General Specifications

Input Ranges

Safe input voltage

range

Input Impedance

(Clamped @ -0.5

VDC to 12 VDC)

10K OHM

Thermistor

Half Bridge

9.59K ohm pulled up to

4.8 VDC

Required Power

(Steady State)

150 mA @ 24 VDC

Required Power

(Inrush)

30 A for 1 ms @ 24 VDC

Nominal Resolution

%AI at 10K Ohm

10 Bits

15,008 counts

Primary Power

Range

10 – 30 VDC

Conversion Speed

All channels converted once

per ladder scan

Relative Humidity

5 to 95% Non-

condensing

Max. Error at 25

°C

reading / ambient

±0.5°F or ±0.3°C

Using specified linearization

in ladder program

Operating

Temperature

-10

°C to +60°C

Terminal Type

Screw Type,5 mm

Removable

Additional error for

reading / ambient

temperatures other

than 25

°C

TBD

CE

UL

See Compliance Table at

http://www.heapg.com/Support/compliance.htm

Filtering

160 Hz hash (noise) filter

1-128 scan digital running

average filter

Weight

12.5 oz. (354.36 g)

Clock Accuracy

+/- One Minute/Month at 20C



















2

Panel Cut-Out and Dimensions


Note: Max. panel thickness: 5 mm.



























3

Ports / Connectors / Cables


Note:

The case of the XLE is black, but for clarity, it is shown in a

lighter gray color.











































Want More Information?

To download the XLE User

Manual (MAN0863), refer

to Technical Support in this

document.

3.62

2 [

9

2m

m

]

3.622 [92mm]

001XLE002

Refer to XLT User
Manual (MAN0863) for
panel box information
and a handy checklist of
requirements.

Note:

The tolerance to meet
NEMA

standards is

± 0.005” (0.1 mm).

To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit.
Lift lid.

CAUTION:

Do not over tighten

screws when screwing the lid
back on.

001ACC009

Power Connector


Power Up:
Connect to Earth Ground.
Apply 10 – 30 VDC.
Screen lights up.

CAN Connector

Use the CAN Connector
when using CsCAN network.

I/O Jumpers (Not Shown):

I/O Jumpers (JP) are located

internally. To access, remove back cover of unit.

Wiring Connectors

(J1 – J4), I/O Jumpers (JP1-3), and DIP

Switches

(RS-485) are described in the DIP Switches, Wiring

and Jumpers

section of this document.

XLT OCS Model: HE-XT103-10

12 Digital DC Inputs / 12 Digital Outputs

2 10K Thermistor Inputs

MJ1

(RS-232 / RS-485)

MJ2

(RS-232 / RS-485)

J1

I/O

Jumper

Memory Slot

001XLE029-R2

J2

I/O

Jumper

NET 1

(CsCAN)

Power

DIP

Switch

Note: The highest usable frequency is 65 KHz for the PWM output