beautypg.com

Horner APG XLe OCS HEXE220C012 User Manual

Horner APG Sensors

background image

MAN0808-09-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________
12/18/2008

Page 1 of 4 ECN # 947








1 Specifications

Specifications

Digital DC Inputs

Inputs per Module

12 including 4 configurable

HSC inputs

Commons per Module

1

Input Voltage Range

12 VDC / 24 VDC

Absolute Max. Voltage

35 VDC Max.

Input Impedance

10 k

Ω

Input Current

Positive Logic

Negative Logic

Upper Threshold

0.8 mA

-1.6 mA

Lower Threshold

0.3 mA

-2.1 mA

Max Upper Threshold

8 VDC

Min Lower Threshold

3 VDC

OFF to ON Response

1 ms

ON to OFF Response

1 ms

HSC Max. Switching Rate

10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width

2.5 kHz Quadrature

Digital Relay Outputs

Outputs per Module

6 relay

Commons per Module

6

Max. Output Current per Relay

3 A at 250 VAC, resistive

Max. Total Output Current

5 A continuous

Max. Output Voltage

275 VAC , 30 VDC

Max. Switched Power

1250 VA, 150 W

Contact Isolation to XLe

ground

1000 VAC

Max. Voltage Drop at Rated

Current

0.5 V

Expected Life

(See Derating section for

chart.)

No load: 5,000,000

Rated load: 100,000

Max. Switching Rate

300 CPM at no load

20 CPM at rated load

Type Mechanical

Contact

Response Time

One update per ladder scan

plus 10 ms

Analog Inputs, Medium Resolution

Number of Channels

4

Input Ranges

0 - 10 VDC

0 – 20 mA

4 – 20 mA

Safe input voltage range

-0.5 V to +12V

Input Impedance

(Clamped @ -0.5 VDC to 12

VDC)

Current

Mode:
100

Ω

Voltage Mode:

500 k

Ω

Nominal Resolution

10 Bits

%AI full scale

32,000 counts

Max. Over-Current

35 mA

Conversion Speed

All channels converted once per

ladder scan

Max. Error at 25

°C

(excluding zero)
*can be made tighter (~0.25%)
by adjusting the digital filter
setting to 3.

4-20 mA 1.00%
0-20 mA 1.00%

0-10 VDC 1.50%*

Additional error for
temperatures other than 25

°C

TBD

Filtering

160 Hz hash (noise) filter

1-128 scan digital running

average filter

General Specifications

Required Power
(Steady State)

130 mA @ 24 VDC

Required Power
(Inrush)

30 A for 1 ms @ 24 VDC

Primary Power
Range

10 – 30 VDC

Relative Humidity

5 to 95% Non-condensing

Clock Accuracy

+/- Seven Minutes/Month at 20C





XLE OCS Model: HE-XE102 / HEXE220C112 / HEXE220C012

12 Digital DC Inputs

4 Analog Inputs (Medium Resolution)

6 Digital Relay Outputs


General Specifications continued

Operating
Temperature

0

°C to +50°C

Terminal Type

Screw Type, 5 mm Removable

Weight

12 oz. (340.19 g)

CE
UL

See Compliance Table at

http://www.heapg.com/Pages/TechSupport/ProductCert.html




2

Panel Cut-Out and Dimensions

Note: Max. panel thickness: 5 mm.

Refer to the XLe/XLt User Manual for panel box information and a handy checklist of requirements.
Note: The tolerance to meet NEMA standards is

± 0.005” (0.1 mm).

















3.

62

2

[9

2m

m

]

3.622 [92mm]

001XLE002

Note – Your keypad overlay

appearance may differ.

Standard US/EU overlays

pictured here for example

.



3

Ports / Connectors / Cables


Note: The case of the XLe is black, but for clarity, it is shown in a lighter gray color.





To Remove Back Cover:
































Power Connector

Power Up:

Connect to Earth Ground.

Apply 10 - 30 VDC.

Screen lights up.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)

CAN Connector

Use the CAN Connector when

using CsCAN network.

Torque Rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)

Unscrew 4 screws located on

the back of the unit.

Remove cover.

CAUTION: Do not over tighten

screws when replacing the back

cover.

I/O Jumpers: (Not Shown):
I/O Jumpers (JP) are located
internally. To access, remove
back cover of unit.

MJ1

(RS-232 / RS-485)

MJ2

(RS-232 / RS-485)

J1

I/O

Jumper

Memory Slot

001XLE029-R2

J2

I/O

Jumper

NET 1

(CsCAN)

Power

DIP

Switch


Wiring Connectors (J1 / J2):
I/O Jumpers (JP1 / JP2),
and
External Jumpers (RS-485) are
described in the Wiring and
Jumpers

section of this

document.

Memory Slot:
Uses Removable Memory for
data logging, screen captures,
program loading and recipes.
Horner Part No.: HE-MC1

Serial Communications:
MJ1
: (RS-232 / RS-485) Use for
Cscape programming and
Application-Defined
Communications.

MJ2:
(RS-232 / RS-485) Use for
Application-Defined
Communications.

Note: Highest usable frequency for PWM output is 65 KHz