1

Specifications

Specifications

Digital DC Inputs

Digital Relay Outputs

Inputs per Module

12 including 4 configurable

HSC inputs

Outputs per Module

6 relay

Commons per Module

1

Commons per Module

6

Input Voltage Range

12 VDC / 24 VDC

Max. Output Current per Relay

3 A at 250 VAC, resistive

Absolute Max. Voltage

35 VDC Max.

Max. Total Output Current

5 A continuous

Input Impedance

10 kΩ

Max. Output Voltage

275 VAC , 30 VDC

Input Current

Positive Logic

Negative Logic

Max. Switched Power

1250 VA, 150 W

Upper Threshold

0.8 mA

-1.6mA

Contact Isolation to XLe ground

1000 VAC

Lower Threshold

0.3 mA

-2.1mA

Max. Voltage Drop at Rated

Current

0.5 V

Max Upper Threshold

8 VDC

Expected Life

(See Derating section for chart.)

No load: 5,000,000

Rated load: 100,000

Min Lower Threshold

3 VDC

Max. Switching Rate

300 CPM at no load

20 CPM at rated load

OFF to ON Response

1 ms

Type

Mechanical Contact

ON to OFF Response

1 ms

Response Time

One update per ladder scan

plus 10 ms

HSC Max. Switching Rate

10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width

2.5 kHz Quadrature

Analog Inputs, Medium Resolution

Number of Channels

4

Input Ranges

0 - 10 VDC

0 – 20 mA

4 – 20 mA

Safe input voltage range

-0.5 V to +12V

Input Impedance

(Clamped @ -0.5 VDC to 12

VDC)

Current Mode:

100 Ω

Voltage

Mode:

500 k Ω

Nominal Resolution

10 Bits

%AI full scale

32,000 counts

Max. Over-Current

35 mA

Conversion Speed

All channels converted once per

ladder scan

Max. Error at 25°C
(excluding zero)

*can be made tighter
(~0.25%) by adjusting the
digital filter setting to 3.

4-20 mA 1.00%
0-20 mA 1.00%

0-10 VDC 1.50%*

Additional error for
temperatures other than 25°C

TBD

Filtering

160 Hz hash (noise) filter

1-128 scan digital running

average filter


2

Wiring and Jumpers
















XL Series Built-in I/O – Model 2 I/O

12 DC Inputs, 6 Relay Outputs, 4 Analog Inputs

for XLe, XLt, XL6 (all models) and XL10e

Wiring Specifications

For I/O wiring (discrete), use the

following wire type or equivalent: Belden

9918, 18 AWG (0.8 mm

2

) or larger.

For shielded Analog I/O wiring, use the

following wire type or equivalent: Belden

8441, 18 AWG (0.8 mm

2

) or larger.

For CAN wiring, use the following wire

type or equivalent: Belden 3084, 24

AWG (0.2 mm

2

) or larger.

Use copper conductors in field wiring

only, 60/75° C

Location of I/O jumpers

(JP1 & JP2) and

wiring connectors

(J1 and J2) with back cover

removed.

Note: The Cscape Module Setup configuration must match the

selected I/O (JP) jumper settings.

001XLE026

JP1 Digital DC In / HSC

Positive Negative

Logic Logic

Default

001XLE027

A1
A2
A3
A4

JP2 Analog In (A1 – A4)

Current Voltage

(20 mA) (10 V)

Default

Note: When using JP2 (A1-A4), each channel can be

independently configured.

Jumper Setting Details