Horner APG XLt OCS HEXT240C015 User Manual
Horner APG Sensors
MAN0873-06-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
12/18/2008
Page 1 of 4 ECN # 947
XLT OCS Model: HE-XT105 / HEXT240C115 / HEXT240C015
12 Digital DC Inputs / 12 Digital DC Outputs
2 Analog Inputs (High Resolution) / 2 Analog Outputs
1
Specifications
Digital DC Inputs
Digital DC Outputs
Inputs per Module
12 including 4 configurable HSC inputs
Outputs per Module
12 including 2 configurable PWM outputs
Commons per Module
1
Commons per Module
1
Input Voltage Range
12 VDC / 24 VDC
Output Type
Sourcing / 10 K Pull-Down
Absolute Max. Voltage
35 VDC Max.
Absolute Max. Voltage
28 VDC Max.
Input Impedance
10 k
Ω
Output Protection
Short Circuit
Input Current
Positive Logic
Negative Logic
Max. Output Current per point
0.5 A
Upper Threshold
0.8 mA
-1.6 mA
Max. Total Current
4 A Continuous
Lower Threshold
0.3 mA
-2.1 mA
Max. Output Supply Voltage
30 VDC
Max Upper Threshold
8 VDC
Minimum Output Supply Voltage
10 VDC
Min Lower Threshold
3 VDC
Max. Voltage Drop at Rated Current
0.25 VDC
OFF to ON Response
1 ms
Max. Inrush Current
650 mA per channel
ON to OFF Response
1 ms
Min. Load
None
OFF to ON Response
1 ms
ON to OFF Response
1 ms
HSC Max. Switching Rate
10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature
Output Characteristics
Current Sourcing (Positive Logic)
Analog Inputs, High Resolution
Number of Channels
2
Thermocouple Temperature
Range
B / R / S
2912
°F to 32.0°F (1600°C to 0°C)
E
1652
°F to -328°F (900°C to -200°C)
Input Ranges
(Selectable)
0 - 10 VDC
0 – 20 mA
4 – 20 mA
100mV
PT100 RTD,
and J, K, N, T, E, R, S, B Thermocouples
T
752.0
°F to -400.0°F (400°C to -240°C)
J
1382.0
°F to -346.0°F (750°C to -210°C)
K / N
2498.0
°F to -400°F (1370°C to -240°C)
Safe input voltage range
10 VDC: -0.5 V to +15 V
20 mA: -0.5 V to +6 V
RTD / T/C: ±24 VDC
Thermocouple Common Mode Range
±10V
Nominal Resolution
10V, 20mA, 100mV: 14 Bits
RTD, Thermocouple: 16 Bits
Converter Type
Delta Sigma
Max. Error at 25
°C
(*excluding zero)
*4-20 mA ±0.10%*
*0-20 mA ±0.10%*
*0-10 VDC ±0.10%*
RTD (PT100) ±1.0 °C
0-100 mV ±0.05%
Input Impedance
(Clamped @ -0.5 VDC to
12 VDC)
Current Mode:
100
Ω, 35mA Max. Continuous
Voltage Mode:
500 k
Ω, 35mA Max. Continuous
Max Thermocouple Error
(After Warm Up Time of One Hour)
±0.2% (±0.3% below -100
°C)
%AI full scale
10 V, 20 mA, 100 mV: 32,000 counts full scale.
RTD / T/C: 20 counts / °C
Conversion Speed, Both Channels
Converted
10V, 20mA, 100mV: 30 Times/Second
RTD, Thermocouple: 7.5 Times/Second
Max. Over-Current
35 mA
Conversion Time per Channel
10V, 20mA, 100mV: 16.7mS
RTD, Thermocouple: 66.7mS
Open Thermocouple
Detect Current
50 nA
RTD Excitation Current
250
μA
Analog Outputs
General Specifications
Number of Channels
2
Required Power
(Steady State)
130 mA @ 24 VDC
Output Ranges
0-10 VDC,
0-20 mA
Required Power (Inrush)
30 A for 1 ms @ 24 VDC
Nominal Resolution
12 Bits
Primary Power Range
10 - 30 VDC
Update rate
Once per PLC scan
Operating Temperature
-10
° to 60° Celsius
Minimum 10 V load
1 k
Ω
Storage Temperature
14 to 140°F (-10 to 60°C)
Maximum 20 mA load
500
Ω
Relative Humidity
5 to 95% Non-condensing
Analog Outputs;
Output Points Required
2 Filtering
15Hz hash (noise) filter
1-128 scan digital running average filter
Terminal Type
Screw Type,5 mm Removable
Maximum Error at 25
°C (excluding
zero)
0.1%
Weight 12.5
oz.
(354.36)
CE
Additional error for temperatures
other than 25
°C
0.01% /
°C
UL
See Compliance Table at
http://www.heapg.com/Pages/TechSupport/ProductCert.html
Clock Accuracy
+/- Seven Minutes/Month at 20C
Note: Highest usable frequency for PWM output is 65 KHz