1 Specifications

Specifications

Digital DC Inputs

XLE103

XLE104

Digital DC

Outputs

XLE103

XLE104

Inputs per Module

12 including 4

configurable

HSC inputs

24 including

4

configurable

HSC inputs

Outputs per

Module

12 including

2

configurable

PWM

outputs

16 including

2

configurable

PWM

outputs

Commons per

Module

1

Commons per
Module

1

Input Voltage

Range

12 VDC / 24 VDC

Output Type

Sourcing / 10 K Pull-Down

Absolute Max.

Voltage

35 VDC Max.

Absolute Max.
Voltage

28 VDC Max.

Input Impedance

10 k

Ω

Output
Protection

Short Circuit

Input Current

Positive

Logic

Negative Logic

Max. Output
Current per
point

0.5 A

Upper Threshold

0.8 mA

-1.6 mA

Max. Total
Current

4 A Continuous

Lower Threshold

0.3 mA

-2.1 mA

Max. Output
Supply Voltage

30 VDC

Max Upper

Threshold

8 VDC

Minimum Output
Supply Voltage

10 VDC

Min Lower

Threshold

3 VDC

Max. Voltage
Drop at Rated
Current

0.25 VDC

OFF to ON

Response

1 ms

Max. Inrush
Current

650 mA per channel

ON to OFF

Response

1 ms

Min. Load

None

HSC Max.

Switching Rate

10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width

2.5 kHz Quadrature

OFF to ON
Response 1

ms

Analog Inputs,

Medium

Resolution

XLE103

XLE104

ON to OFF
Response 1

ms

Number of
Channels

2 2

Output
Characteristics

Current Sourcing (Pos logic)

General Specifications

Input Ranges
Safe input voltage
range
Input Impedance
(Clamped @ -0.5
VDC to 12 VDC)

0 - 10 VDC

0 – 20 mA
4 – 20 mA

-0.5 V to +12V
Current Mode:

100

Ω

Voltage Mode:

500 k

Ω

Required Power
(Steady State)

130 mA @ 24 VDC

Required Power
(Inrush)

30 A for 1 ms @ 24 VDC

Nominal Resolution
%AI full scale
Max. Over-Current

10 Bits

32,000 counts

35 mA

Primary Power
Range

10 – 30 VDC

Conversion Speed

All channels converted once

per ladder scan

Relative Humidity

5 to 95% Non-

condensing

Max. Error at 25

°C

(excluding zero)

4-20 mA 1.00%
0-20 mA 1.00%
0-10 VDC 0.50%

Operating
Temperature

0

°C to +50°C

Terminal Type

Screw Type,5 mm

Removable

Additional error for
temperatures other
than 25

°C

TBD

CE

UL

See Compliance Table at

http://www.heapg.com/Pages/TechSupport/Prod
uctCert.html

Filtering

160 Hz hash (noise) filter

1-128 scan digital running

average filter

Weight

12.5 oz. (354.36 g)

Clock

Accuracy

+/- Seven

Minutes/Month at 20C

Note: Highest usable frequency for PWM output is 65 KHz










XLE OCS Model:

XLE OCS Model:

HE-XE104 / HEXE220C114 / HEXE220C014

HE-XE103 / HEXE220C113 / HEXE220C013

24 Digital DC Inputs / 16 Digital Outputs

12 Digital DC Inputs / 12 Digital Outputs

2 Analog Inputs (Medium Resolution)

2 Analog Inputs (Medium Resolution)

2

Panel Cut-Out and Dimensions


Note: Max. panel thickness: 5 mm.

3.62

2

[

9

2m

m

]

3.622 [92mm]

001XLE002


























Refer to the XLe/XLt

User Manual for panel

box information and a

handy checklist of

requirements.

3

Ports / Connectors / Cables


Note: The case of the XLe is black, but for clarity, it is shown in a
lighter gray color.











































Note:

The tolerance to meet

NEMA standards is

± 0.005” (0.1 mm).

Note – Your keypad overlay

appearance may differ.

Standard US/EU overlays

pictured here for example

.

MJ1

(RS-232 / RS-485)

MJ2

(RS-232 / RS-485)

J1

I/O

Jumper

Memory Slot

001XLE029-R2

J2

I/O

Jumper

NET 1

(CsCAN)

Power

DIP

Switch

To Remove Back Cover:

Unscrew 4 screws located on

the back of the unit and remove

back cover.

CAUTION: Do not over tighten

screws when replacing the back

cover.

001ACC009

Power Connector

Power Up:

Connect to Earth Ground.

Apply 10 – 30 VDC.

Screen lights up.

Torque rating 4.5 - 7 Lb-In

(0.50 – 0.78 N-m)

CAN Connector

Use the CAN Connector

when using CsCAN network.

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)

I/O Jumpers (Not Shown): I/O Jumpers (JP) are located
internally. To access, remove back cover of unit.

Wiring Connectors (J1 – J4), I/O Jumpers (JP1-3), and
External Jumpers (RS-485) are described in the Wiring and
Jumpers
section of this document.