beautypg.com

Horner APG XL4 OCS User Manual

Xl4 ocs, 1 specifications 2 dimensions & panel cutout

background image

MAN0963-07EN

Specifications / Installation

XL4 OCS

Datasheet for

HE-XC1E0, HE-XC1E2, HE-XC1E3, HE-XC1E4, HE-XC1E5

HEXT251C100, HEXT251C112, HEXT251C113, HEXT251C114, HEXT251C115

General Specifications

Control & Logic Specifications

Required Power

(Steady state)

95 mA @ 24 VDC

190 mA @ 12 VDC

Control Language Support

Advanced Ladder Logic

Full IEC 1131-3 Languages

Required Power

(Inrush)

2A for <1 ms @ 24 VDC

DC Switched

Logic Program Size

& Logic Scan Rate

1MB, maximum

0.013mS/K

Primary Power Range

10 – 30 VDC

Online Programming Changes

Supported in Advanced Ladder

Relative Humidity

5 to 95% Non-condensing

I/O Support

Digital Inputs

2048

Clock Accuracy

+/- 20 ppm maximum at 25°

C

(+/- 1 Minutes per Month)

Digital Outputs

2048

Analog Inputs

512

Surrounding Air Temp

-10°C to +60°C

Analog Outputs

512

Storage Temp

-30°C to +70°C

General Purpose Registers

50,000 (words) Retentive

Weight

12 oz. (340 g)

16,384 (bits) Retentive

UL / CE

USA: http://www.heapg.com/Pages/TechSupport/ProductCert.html

16,384 (bits) Non-retentive

Europe: http://www.horner-apg.com/en/support/certification.aspx

Display Specifications

Connectivity

Display Type

3.5” TFT Transmissive Color

Serial Ports

1 RS-232 & 1 RS-485 on single Modular Jack

Resolution

QVGA (320x240)

USB mini-B

USB 2.0 (480MHz) Programming & Data Access

Color

16-bit (65,535)

USB A

USB 2.0 (480MHz) for USB FLASH Drives (2TB)

Screen Memory

64MB

CAN

Remote I/O, Peer-to-Peer Comms, Cscape

User-Programmable

Screens

1023

Ethernet

10/100 Mb (Auto-MDX)

Modbus TCP C/S, HTTP, FTP, SMTP, Cscape

Backlight

LED – 50,000 hour life

Remote I/O

SmartRail, SmartStix, SmartBlock, SmartMod

Screen Update Rate

User Configurable within the scan time.

(perceived as instantaneous in many cases)

Removable

Memory

MicroSD, support for >32GB max.

Application Updates, Datalogging, more

Input / Output Specifications

Model

DC In

DC

Out

Relays

HS In

HS Out

mA/V

In

mA/V

RTD/Tc

mA/V

Out

High-Speed Counters

Number of Counters

2

Model 2

12

6

4

4

Maximum Frequency

>500kHz each

Model 3

12

12

4

2

2

Accumulator Size

32-bits each

Model 4

24

16

4

2

2

Modes Supported

Model 5

12

12

4

2

2

2

Totalizer

Quadrature

There are 4 high-speed inputs of the total DC Inputs. There are 2 high-speed outputs of the total

DC outputs. Model 2, 3 & 4 feature 12-bit Analog I/O. Model 5 features 14/16-bit Analog I/O.

High-speed Outputs can be used for PWM and Pulse Train Outputs, currently limited to <65kHz.

Pulse Meas.

Frequency Meas.

2 Position Controlled Outputs

1 ON/OFF Setpoint per Output

1 Specifications

2 Dimensions & Panel Cutout

Cutout tolerance to meet NEMA

standards is ±0.005” (0.1mm).

Max. Panel Thickness is 5mm.

Panel Cutout

August 23, 2012

Specifications / Installation

Page 1 of 6

3

.6

2

2

[9

2

m

m

]

3.622 [92mm]

001XLE002