Horner APG XL10e OCS Built-in I/O Model 5 I/O User Manual
Xl series built-in i/o – model 5 i/o
MAN0953-02-EN
Specifications / Installation
1/6/2011
Page 1 of 4
1
Specifications
Specifications
Digital DC Inputs
Digital DC Outputs
Inputs per Module
12 including 4 configurable HSC inputs
Outputs per Module
12 including 2 configurable PWM outputs
Commons per Module
1
Commons per Module
1
Input Voltage Range
12 VDC / 24 VDC
Output Type
Sourcing / 10 K Pull-Down
Absolute Max. Voltage
35 VDC Max.
Absolute Max. Voltage
28 VDC Max.
Input Impedance
10 kΩ
Output Protection
Short Circuit
Input Current
Positive Logic
Negative Logic
Max. Output Current per point
0.5 A
Upper Threshold
0.8 mA
-1.6 mA
Max. Total Current
4 A Continuous
Lower Threshold
0.3 mA
-2.1 mA
Max. Output Supply Voltage
30 VDC
Max Upper Threshold
8 VDC
Minimum Output Supply Voltage
10 VDC
Min Lower Threshold
3 VDC
Max. Voltage Drop at Rated Current
0.25 VDC
OFF to ON Response
1 ms
Max. Inrush Current
650 mA per channel
ON to OFF Response
1 ms
Min. Load
None
OFF to ON Response
1 ms
ON to OFF Response
1 ms
HSC Max. Switching Rate
10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature
Output Characteristics
Current Sourcing (Positive Logic)
Analog Inputs, High Resolution
Number of Channels
2
Thermocouple
Temperature Range
B / R / S
2912°F to 32.0°F (1600°C to 0°C)
E
1652°F to -328°F (900°C to -200°C)
Input Ranges
(Selectable)
0 - 10 VDC
0 – 20 mA
4 – 20 mA
100mV
PT100 RTD,
and J, K, N, T, E, R, S, B Thermocouples
T
752.0°F to -400.0°F (400°C to -240°C)
J
1382.0°F to -346.0°F (750°C to -210°C)
K / N
2498.0°F to -400°F (1370°C to -240°C)
Safe input voltage range
10 VDC: -0.5 V to +15 V
20 mA: -0.5 V to +6 V
RTD / T/C: ±24 VDC
Thermocouple Common Mode Range
±10V
Nominal Resolution
10V, 20mA, 100mV: 14 Bits
RTD, Thermocouple: 16 Bits
Converter Type
Delta Sigma
Max. Error at 25°C
(*excluding zero)
*4-20 mA ±0.10%*
*0-20 mA ±0.10%*
*0-10 VDC ±0.10%*
RTD (PT100) ±1.0 °C
0-100 mV ±0.05%
Input Impedance
(Clamped @ -0.5 VDC to 12
VDC)
Current Mode:
100 Ω, 35mA Max. Continuous
Voltage Mode:
500 kΩ, 35mA Max. Continuous
Max Thermocouple Error
(After Warm Up Time of One Hour)
±0.2% (±0.3% below -100°C)
%AI full scale
10 V, 20 mA, 100 mV: 32,000 counts full scale.
RTD / T/C: 20 counts / °C
Conversion Speed, Both Channels
Converted
10V, 20mA, 100mV: 30 Times/Second
RTD, Thermocouple: 7.5 Times/Second
Max. Over-Current
35 mA
Conversion Time per Channel
10V, 20mA, 100mV: 16.7mS
RTD, Thermocouple: 66.7mS
Open Thermocouple Detect
Current
50 nA
RTD Excitation Current
250 µA
Analog Outputs
Number of Channels
2
Minimum 10 V load
1 kΩ
Output Ranges
0-10 VDC, 0-20 mA
Maximum 20 mA load
500 Ω
Nominal Resolution
12 Bits
Analog Outputs; Output Points Required
2
Update rate
Once per PLC scan
Maximum Error at 25°C (excluding zero)
0.1%
Additional error for temperatures other than 25°C
0.01% / °C
2
Wiring and Jumpers
XL Series Built-in I/O – Model 5 I/O
12 DC Inputs, 12 DC Outputs, 2 Universal Analog In & 2 Analog Out
for XLe, XLt, XL6 (all models) and XL10e
Wiring Specifications
For I/O wiring (discrete), use the following wire type or
equivalent: Belden 9918, 18 AWG (0.8 mm
2
) or larger.
For shielded Analog I/O wiring, use the following wire type or
equivalent: Belden 8441, 18 AWG (0.8 mm
2
) or larger.
For CAN wiring, use the following wire type or equivalent:
Belden 3084, 24 AWG (0.2 mm
2
) or larger.
Use copper conductors in field wiring only, 60/75° C
Location of I/O jumpers
(JP1, JP2, JP3 & JP4) and
wiring connectors
(J1, J2 & J3) with back cover
removed.
Jumper Location Details