beautypg.com

GW Instek PSW-Series User Manual User Manual

Page 125

background image

ANALOG CONTROL

125

Note

The Ext-R

configuration is recommended for

safety reasons. In the event that the cables become
accidentally disconnected, the voltage output will
drop to zero. Under similar circumstances using
Ext-R , an unexpected high voltage would be
output.

If switches are used to switch between fixed
resistances, use switches that avoid creating open
circuits. Use short-circuit or continuous resistance
switches.

Connection

PSW

EXT-R

Analog

connector

7

6

Output

Terminal

2 core shielded

wire or twisted

pair

Pin6 → EXT-R

Pin7 → EXT-R

Wire shield → negative (-) output terminal

Steps

1. Connect the external resistance according to the

connection diagrams above.

2. Set the F-90 (CV Control)

configuration settings to 2 for Ext-
R or 3 for Ext-R .

Page 114

Be sure to cycle the power after the power
on configuration has been set.

3. Press the Function key and confirm

the new configuration settings (F-
90=2 or 3).

Function