Watlow EZ-ZONE PM User Manual
Page 83
Watlow EZ-ZONE
®
PM Limit Controller
•
80
•
Chapter 8 Features
** Diagnostic Menu and all associated prompts are always visible and never writable.
Lockout Security [SLoC] & [rloC]
Factory Page Menu Parameters
Parameters
Security Level
0
1
2
3
4
5
[LoC;O]
N Y
Y Y Y
Y
[ pas ; e]
N Y
Y Y Y
Y
[rloC]
Y Y
Y Y Y
Y
[sloC]
Y Y
Y Y Y
Y
Note:
When using Method 1 Lockout all settings can be modified by anyone who knows how to find their way to
the [SLoC] and [rloC] parameters
Using Lockout Method 2 (Password Enable)
It is sometimes desirable to apply a higher level of security to the control where a password would be required
to access the control. If Password Enabled [pas;e] in the Factory Page under the [`loC] Menu is set to on,
an overriding Password Security will be in effect. Without the appropriate password, specified menus will re-
main inaccessible. Page and Menu access is defined in the Locked Access Level [loC;L] prompt. On the other
hand, a User with a password would have visibility restricted by the Read Lockout Security [rloC]. As an
example, with Password Enabled and the Locked Access Level [loC;L] set to 1 and [rloC] is set to 3, the
available Pages for a User without a password would be limited to the Home and Factory Pages (locked level
1). If the User password is entered all pages would be accessible with the exception of the Setup Page as de-
fined by level 3 access.
How to Enable Password Security
Follow the steps below:
1. Go to the Factory Page by holding down the Reset
RESET
key and the Advance
‰
key for approximately six sec-
onds.
2. Push the Down ¯ key one time to get to the [`loC] menu. Again push the Advance
‰
key until the Pass-
word Enabled [pas;e] prompt is visible.
3. Push either the up or down key to turn it on. Once on, 4 new prompts will appear:
a. [loC;l] , Locked Access Level (1 to 5) corresponding to the lockout table above.
b. [roll] , Rolling Password will change the Cus-tomer Code every time power is cycled.
c. [pas;u] , User Password which is needed for a Us-er to acquire access to the control.
d. [pas;a] , Administrator Password which is need-ed to acquire administrative access to the control.
The Administrator can either change the User and or the Administrator password or leave them in the de-
fault state. Once Password Security is enabled they will no longer be visible to anyone other than the Admin-
istrator. In other words the Lock Menu [`loC] is not available to a User. As can be seen in the formula that
follows either the User or Administrator will need to know what those passwords are to acquire a higher level
of access to the control. Back out of this menu by pushing the Infinity ˆ key. Once out of the menu, the Pass-
word Security will be enabled.
How to Acquire Access to the Control
To acquire access to any inaccessible Pages or Menus, go to the Factory Page and enter the [UloC] menu.
Once there follow the steps below:
Note:
If Password Security (Password Enabled [pas;e] is On) is enabled the two prompts mentioned below in
the first step will not be visible. If the password is unknown, call the individual or company that originally
setup the control.
1. Acquire either the User Password [pas;u] or the Administrator Password [pas;a].
2. Push the Advance
‰
key one time where the Code [Code] prompt will be visible.