Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss

of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation be-

tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.

Note:

The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.

Watlow EZ-ZONE

®

PM Limit Controller

28

Chapter 2 Install and Wire

Network Status

Indicator State

Summary

Requirement

Steady Off

Not powered, no IP address

If the device does not have an

IP address (or is powered off),

the network status indicator

shall be steady off.

Flashing Green

No connections

If the device has no estab-

lished connections, but has

obtained an IP address, the

network status indicator shall

be flashing green.

Steady Green

Connected

If the device has at least one

established connection (even

to the Message Router), the

network status indicator shall

be steady green.

Flashing Red

Connection timeout

If one or more of the connec-

tions in which this device is

the target has timed out, the

network status indicator shall

be flashing red. This shall be

left only if all timed out con-

nections are reestablished or

if the device is reset.

Steady Red

Duplicate IP

If the device has detected

that its IP address is already

in use, the network status in-

dicator shall be steady red.

Flashing Green /

Red

Self-test

While the device is perform-

ing its power up testing, the

network status indicator shall

be flashing green / red.

Module Status

Indicator State

Summary

Requirement

Steady Off

No power

If no power is supplied to the device, the module

status indicator shall be steady off.

Steady Green

Device operational

If the device is operating correctly, the module

status indicator shall be steady green.

Flashing Green

Standby

If the device has not been configured, the module

status indicator shall be flashing green.

Flashing Red

Minor fault

If the device has detected a recoverable minor

fault, the module status indicator shall be flash-

ing red.

NOTE: An incorrect or inconsistent configuration

would be considered a minor fault.

Steady Red

Major fault

If the device has detected a non-recoverable major

fault, the module status indicator shall be steady

red.

Flashing Green / Red Self-test

While the device is performing its power up test-

ing, the module status indicator shall be flashing

green / red.

Link Status

Indicator State

Summary

Requirement

Steady Off

Not powered,

unknown link speed

If the device cannot determine link speed

or power is off, the network status indicator

shall be steady off.

Green

- - - -

If cable is wired and connected correctly, the

LED will be Green.