Digital input/output menu – Watlow EZ-ZONE PM User Manual
Page 53
Watlow EZ-ZONE
®
PM Limit Controller
•
50
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`i;Ca]
[ i.CA]
Analog Input (1)
Calibration Offset *
Offset the input reading
to compensate for lead
wire resistance or other
factors that cause the
input reading to vary
from the actual process
value.
-1,999.000 to 9,999.000°F or
units
-1,110.555 to 5,555.000°C
0.0
Instance 1
Map 1 Map 2
382
382
0x68 (104)
1
0x0C (12)
2
4012
float
RWES
[`Ain]
[ Ain]
Analog Input (1)
Analog Input Value *
View the process value.
Note:
Ensure that the Input
Error Status (below)
indicates no error (61)
when reading this
value using a field bus
protocol. If an error
exists, the last known
value prior to the er-
ror occurring will be
returned.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
Instance 1
Map 1 Map 2
360
360
0x68 (104)
1
1
0
4001
float
R
[`i;Er]
[ i.Er]
Analog Input (1)
Input Error Status *
View the cause of the
most recent error. If
the [Attn] message is
[Er;i1]
, this parameter
will display the cause of
the input error.
[nonE]
None (61)
[OPEn]
Open (65)
[Shrt]
Shorted (127)
[`E;M]
Measurement Error
(149)
[E;CAL]
Bad Calibration Data
(139)
[Er;Ab]
Ambient Error (9)
[E;;Rtd]
RTD Error (141)
[FAiL]
Fail (32)
[Nsrc]
Not Sourced (246)
None
Instance 1
Map 1 Map 2
362
362
0x68 (104)
1
2
1
4002
float
R
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output
(5 to 6)
Digital I/O Direction
Set this function to
operate as an input or
output.
[OtPt]
Output (68)
[iCon]
Input Dry Contact
(44)
[``in]
Input Voltage (193)
Output
Instance 5
Map 1 Map 2
1000
1120
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
1
82
6001
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
*
These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User Set