beautypg.com

Input 1 thermocouple, Input 1 rtd, Input 1 process – Watlow EZ-ZONE PM User Manual

Page 23: Input 1 potentiometer

background image

Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss

of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation be-

tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.

Note:

The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.

Watlow EZ-ZONE

®

PM Limit Controller

20

Chapter 2 Install and Wire

Input 1 Thermocouple

-

+

Thermocouple

(Input 1)

L1
K1
J1
L2
K2
T1

S1
R1

Slot A

• 2K Ω maximum source resistance
• >20 MΩ input impedance
• 3 microampere open-sensor detection
• Thermocouples are polarity sensitive. The negative lead (usually

red) must be connected to S1.

• To reduce errors, the extension wire for thermocouples must be

of the same alloy as the thermocouple.

Input 1: PM _ _ _ _ _ - _ _ _ _ _ _ _ (S1/R1)

Input 1 RTD

2-wire

RTD

(Input 1)

L1
K1
J1
L2
K2
T1

S1
R1

S1

S3

Slot A

3-wire

RTD

(input 1)

L1
K1
J1
L2
K2

T1
S1
R1

S1

S2

S3

Slot A

• platinum, 100 and 1,000 Ω @ 0°C
• calibration to DIN curve (0.00385 Ω/Ω/°C)
• 20 Ω total lead resistance
• RTD excitation current of 0.09 mA typical. Each

ohm of lead resistance may affect the reading by

0.03°C.

• For 3-wire RTDs, the S1 lead (usually white) must

be connected to R1.

• For best accuracy use a 3-wire RTD to compensate

for lead-length resistance. All three lead wires must

have the same resistance.

PM _ _ _ _ _-_ _ _ _ AAA (all)

Input 1 Process

-

+

L1
K1
J1
L2
K2
T1

S1
R1

volts

Process

(Input 1)

Slot A

-

+

T_
S_

amperes

Slot A

• 0 to 20 mA @ 100 Ω input impedance
• 0 to 10VÎ (dc) @ 20 kΩ input impedance
• 0 to 50 mVÎ (dc) @ 20 kΩ input impedance
• scalable
PM _ _ _ _ _-_ _ _ _ AAA (all)

Input 1 Potentiometer

pot

(input 1)

L1
K1
J1
L2
K2
T1

S1
R1

Slot A

CW

CCW

• Use a 1 kΩ potentiometer.