Watlow EZ-ZONE
®
PM Limit Controller
•
70
•
Chapter 7 Factory Page
Factory Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[ELi;o]
[ELi.o]
Calibration (1)
Electrical Input Offset
Change this value to
calibrate the low end of
the input range.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1
Map 2
378
378
0x68 (104)
1
0xA (10)
- - - -
4010
float
RWES
[ELi;S]
[ELi.S]
Calibration (1)
Electrical Input Slope
Adjust this value to cali-
brate the slope of the
input value.
-1,999.000 to 9,999.000
1.0
Instance 1
Map 1
Map 2
380
380
0x68 (104)
1
0xB (11)
- - - -
4011
float
RWES
[ELo;o]
[ELo.o]
Calibration (3)
Electrical Output
Offset
Change this value to
calibrate the low end of
the output range.
Menu 2 calibrates out-
put 3.
-1,999.000 to 9,999.000
0.0
Instance 1
Map 1
Map 2
808
928
0x76 (118)
3
5
- - - -
18005
float
RWES
[ELo;S]
[ELo.S]
Calibration (3)
Electrical Output
Slope
Adjust this value to cali-
brate the slope of the
output value.
Menu 2 calibrates out-
put 3.
-1,999.000 to 9,999.000
1.0
Instance 1
Map 1
Map 2
730
850
0x76 (118)
3
6
- - - -
18006
float
RWES
[``Pn]
[ Pn]
Calibration (1 to 2)
Part Number
Displays current set-
ting for control model
number.
[fCty]
Factory
[User]
User
Factory
- - - -
- - - -
- - - -
- - - -
uint
R
[Code]
[CodE]
Calibration (1 to 3)
Public Key
Changes the control to a
PM Express or back to
original model number
as shown on the side of
the control.
[2501]
PM Express
[`606]
Factory model
number
4999
- - - -
- - - -
- - - -
- - - -
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set