Output 3 universal process, Output 3 solid-state relay, form a, Output 4 switched dc – Watlow EZ-ZONE PM User Manual

Page 27

background image

Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss

of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation be-

tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.

Note:

The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.

Watlow EZ-ZONE

®

PM Limit Controller

24

Chapter 2 Install and Wire

Output 3 Universal Process

Universal Process

(Output 3)

volts or current -

current +

volts +

F3
G3
H3

L4
K4
T2
S2
R2

Slot B

• 0 to 20 mA into 800 Ω maxi-

mum load

• 0 to 10VÎ (dc) into 1 kΩ mini-

mum load

• scalable
• output supplies power
• cannot use voltage and current

outputs at same time

• Output may be used as retrans-

mit or control.

PM _ _ _ _ _-_ _ [F] _ AAA

negative

volts +

current +

4 to 20 mA

0 to 10 V

F_

G_

H_

Output 3 Solid-State Relay, Form A

normally open

common

L3

K3

L4

K4

T2

S2

R2

Slot B

• 0.5 A at 20 to 264VÅ (ac) maxi-

mum resistive load

• 20 VA 120/240VÅ (ac) pilot duty
• opto-isolated, without contact

suppression

• maximum off state leakage of

105 microamperes

• output does not supply power
• Do not use on dc loads.
• See Quencharc note.
PM _ _ _ _ _ -_ _ [K] _ AAA

K_

L_

1.1

0

-20

50

40

30

20

10

0

-10

60

70

Amps RMS

Ambient Temperature (

o

C)

0.1

1

0.2

0.9

0.3

0.4

0.5

0.6

0.7

0.8

1 Amp SSR Derating Curve

Sa

fe

Operating Area

Output 4 Switched DC

Mechanical Relay

(Output 4)

dc+

dc-

L3

K3

J3

W4

Y4

T2
S2

R2

Slot B

• 10 mA DC maximum supply

current

• Short circuit limited to <50 mA
• 22 to 32VÎ (dc) open circuit

voltage

• Use dc- and dc+ to drive exter-

nal solid-state relay.

• DIN-A-MITE compatible
• Single-pole: up to 2 in series,

none in parallel

PM _ _ _ _ _-_ _ _ [C] AAA

common

24V

X_

dc +

dc -

W_

Y_

Quencharc Note:

Switching pilot duty inductive loads

(relay coils, solenoids, etc.) with the

mechanical relay, solid state relay

or open collector output options

requires use of an R.C. suppressor.