beautypg.com

Output 1 switched dc/open collector, Output 1 mechanical relay, form c – Watlow EZ-ZONE PM User Manual

Page 25

background image

Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss

of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation be-

tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.

Note:

The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.

Watlow EZ-ZONE

®

PM Limit Controller

22

Chapter 2 Install and Wire

Digital Output 5, 6

98
99

CF

CD

CE

B5

D6
D5

Slot C

Digital Output
• Update rate 10 Hz
• Output voltage 24V
• Current limit, Output 5, 24

mA maximum

• Current limit, Output 6,

10 mA maximum driving

single pole DIN-A-MITE

• *Capable of driving a 3-pole

DIN-A-MITE

• Open-circuit voltage 22 to

32VÎ (dc)

PM _ _ [2, 4] _ _-_ _ _ _ _ _ _

* Output 5 only

24 Vdc

common

_

B

D

_

Output 1 Switched DC/Open Collector

dc - (open collector)

dc +

common

X1

W1

Y1

L2

K2
T1
S1
R1

Slot A

Switched DC
• 30 mA dc maximum supply cur-

rent

• Short circuit limited to <50 mA
• 22 to 32VÎ (dc) open circuit

voltage

• Use dc- and dc+ to drive exter-

nal solid-state relay.

• DIN-A-MITE compatible
• Single-pole: up to 4 in parallel

or 4 in series

• 2-pole: up to 2 in parallel or 2

in series

• 3-pole: up to 2 in series
Open Collector
• 100 mA maximum output cur-

rent sink

• 30VÎ (dc) maximum supply

voltage

• Any switched dc output can

use the common terminal.

• Use an external power supply

to control a dc load, with the

load positive to the positive

of the power supply, the load

negative to the open collector

and common to the power sup-

ply negative.

PM _ _ _ [C] _-_ _ _ _ AAA

Switched DC

common

24V

X_

dc +

dc -

W_

Y_

Open Collector

Load

Power Supply

dc -

common

24V

X_

W_

Y_

Output 1 Mechanical Relay, Form C

Mechanical Relay

(Output 1)

normally open

normally closed

common

L1
K1
J1

L2
K2
T1
S1
R1

Slot A

• 5 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mA at 24V minimum load
• 125 VA pilot duty at 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
PM _ _ _ [E] _-_ _ _ _ AAA

normally open

common

normally closed

L _

K _

J _

Quencharc Note:

Switching pilot duty inductive

loads (relay coils, solenoids,

etc .) with the mechanical

relay, solid state relay or

open collector output options

requires use of an R .C . sup-

pressor .