beautypg.com

Analog input menu, Digital input/output menu, Analog input menu digital input/output menu – Watlow EZ-ZONE PM User Manual

Page 45

background image

Watlow EZ-ZONE

®

PM Limit Controller

42

Chapter 5 Operations Page

Operations Page

Dis-

play

Parameter Name

Description

Range

Default Modbus Rela-

tive Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[``Ai]
[oPEr]
Analog Input Menu

[`Ain]
[ Ain]

Analog Input (1)

Analog Input Value

View the process value.

Note:

Ensure that the Input Er-

ror (below) indicates no

error (61) when reading

this value using a field

bus protocol. If an error

exists, the last known

value prior to the error oc-

curring will be returned.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

- - - -

Instance 1

Map 1 Map 2

360

360

0x68 (104)

1

1

0

4001

float

R

[`i;Er]
[ i.Er]

Analog Input (1)

Input Error

View the cause of the most

recent error. If the [Attn]

message is [Er;i1], this

parameter will display the

cause of the input error.

[nonE]

None (61)

[OPEn]

Open (65)

[FAiL]

Fail (32)

[Shrt]

Shorted (127)

[`E;M]

Measurement

Error (140)

[E;CAL]

Bad Calibration

Data (139)

[Er;Ab]

Ambient Er-

ror (9)

[E;;Rtd]

RTD Error (141)

[Nsrc]

Not Sourced

(246)

None

Instance 1

Map 1

Map 2

362

362

0x68 (104)

1

2

1

4002

uint

R

[`i;Ca]
[ i.CA]

Analog Input (1)

Calibration Offset

Offset the input reading to

compensate for lead wire

resistance or other factors

that cause the input reading

to vary from the actual pro-

cess value.

-1,999.000 to

9,999.000°F or units

-1,110.555 to

5,555.000°C

0.0

Instance 1

Map 1

Map 2

382

382

0x68 (104)

1

0xC (12)

2

4012

float

RWES

[`dio]
[oPEr]
Digital Input/Output Menu

[`do;S]
[ do.S]

Digital Output (5 to 6)

Output State

View the state of this out-

put.

[`off]

Off (62)

[``on]

On (63)

- - - -

Instance 5

Map 1

Map 2

1012

1132

Offset to next

instance equals

+30

0x6A (106)

5 to 6

7

90

6007

uint

R

[`di;S]
[ di.S]

Digital Input (5 to 6)

Input State

View this event input state.

[`off]

Off (62)

[``on]

On (63)

- - - -

Instance 5

Map 1

Map 2

1020

1140

Offset to next

instance equals

+30

0x6A (106)

5 to 6

0xB (11)

- - - -

6011

uint

R

Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.

R: Read

W: Write

E: EEPROM

S: User

Set