Analog input menu, Digital input/output menu, Analog input menu digital input/output menu – Watlow EZ-ZONE PM User Manual
Page 45
![background image](/manuals/359082/45/background.png)
Watlow EZ-ZONE
®
PM Limit Controller
•
42
•
Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter Name
Description
Range
Default Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[``Ai]
[oPEr]
Analog Input Menu
[`Ain]
[ Ain]
Analog Input (1)
Analog Input Value
View the process value.
Note:
Ensure that the Input Er-
ror (below) indicates no
error (61) when reading
this value using a field
bus protocol. If an error
exists, the last known
value prior to the error oc-
curring will be returned.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - -
Instance 1
Map 1 Map 2
360
360
0x68 (104)
1
1
0
4001
float
R
[`i;Er]
[ i.Er]
Analog Input (1)
Input Error
View the cause of the most
recent error. If the [Attn]
message is [Er;i1], this
parameter will display the
cause of the input error.
[nonE]
None (61)
[OPEn]
Open (65)
[FAiL]
Fail (32)
[Shrt]
Shorted (127)
[`E;M]
Measurement
Error (140)
[E;CAL]
Bad Calibration
Data (139)
[Er;Ab]
Ambient Er-
ror (9)
[E;;Rtd]
RTD Error (141)
[Nsrc]
Not Sourced
(246)
None
Instance 1
Map 1
Map 2
362
362
0x68 (104)
1
2
1
4002
uint
R
[`i;Ca]
[ i.CA]
Analog Input (1)
Calibration Offset
Offset the input reading to
compensate for lead wire
resistance or other factors
that cause the input reading
to vary from the actual pro-
cess value.
-1,999.000 to
9,999.000°F or units
-1,110.555 to
5,555.000°C
0.0
Instance 1
Map 1
Map 2
382
382
0x68 (104)
1
0xC (12)
2
4012
float
RWES
[`dio]
[oPEr]
Digital Input/Output Menu
[`do;S]
[ do.S]
Digital Output (5 to 6)
Output State
View the state of this out-
put.
[`off]
Off (62)
[``on]
On (63)
- - - -
Instance 5
Map 1
Map 2
1012
1132
Offset to next
instance equals
+30
0x6A (106)
5 to 6
7
90
6007
uint
R
[`di;S]
[ di.S]
Digital Input (5 to 6)
Input State
View this event input state.
[`off]
Off (62)
[``on]
On (63)
- - - -
Instance 5
Map 1
Map 2
1020
1140
Offset to next
instance equals
+30
0x6A (106)
5 to 6
0xB (11)
- - - -
6011
uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set