Watlow ez-zone, Pm limit controller, Chapter 7 factory page – Watlow EZ-ZONE PM User Manual
Page 70

Watlow EZ-ZONE
®
PM Limit Controller
•
67
•
Chapter 7 Factory Page
Factory Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[rLoC]
[rLoC]
Security Setting
Read Lock
Set the read security
clearance level. The
user can access the
selected level and all
lower levels.
If the Set Lockout Secu-
rity level is higher than
the Read Lockout Secu-
rity, the Read Lockout
Security level takes
priority.
1 to 5
5
Instance 1
Map 1 Map 2
1848 2318
0x67 (103)
1
0x0A (10)
- - - -
3010
uint
RWE
[SLoC]
[SLoC]
Security Setting
Write Security
Set the write security
clearance level. The
user can access the
selected level and all
lower levels.
If the Set Lockout Secu-
rity level is higher than
the Read Lockout Secu-
rity, the Read Lockout
Security level takes
priority.
0 to 5
5
Instance 1
Map 1 Map 2
1844 2314
0x67 (103)
1
0x0B (11)
- - - -
3011
uint
RWE
[loC;l]
[LoC.L]
Security Setting
Locked Access Level
Determines user level
menu visibility when
security is enabled. See
Features section under
Password Security.
1 to 5
5
- - - -
- - - -
- - - -
3016
uint
RWE
[roll]
[roLL]
Security Setting
Rolling Password
When power is cycled
a new Public Key will
be displayed and User
Password changes.
[`off]
Off
[``on]
On
Off
- - - -
- - - -
- - - -
3019
uint
RWE
[pas;u]
[PAS.u]
Security Setting
User Password
Used to acquire access
to menus made avail-
able through the Locked
Access Level setting.
10 to 999
63
- - - -
- - - -
- - - -
3017
uint
RWE
[pas;a]
[PAS.A]
Security Setting
Administrator Pass-
word
Used to acquire full ac-
cess to all menus includ-
ing disabling or chang-
ing passwords.
10 to 999
156
- - - -
- - - -
- - - -
3018
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set