Communications menu – Watlow EZ-ZONE PM User Manual
Page 62
Watlow EZ-ZONE
®
PM Limit Controller
•
59
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[2one]
[Zone]
Global
Zone
Turns Zone LED on or
off based on selection.
[`off]
Off (62)
[``on]
On (63)
On
Instance 1
Map 1 Map 2
- - - -
2350
0x6A (103)
1
0x1A (26)
- - - -
3026
uint
RWES
[Chan]
[Chan]
Global
Channel
Turns Channel LED on
or off based on selection.
[`off]
Off (62)
[``on]
On (63)
On
Instance 1
Map 1 Map 2
- - - -
2352
0x6A (103)
1
0x1B (27)
- - - -
3027
uint
RWES
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of
Display Pairs.
1 to 10
2
Instance 1
Map 1 Map 2
- - - -
2354
0x6A (103)
1
0x1C (28)
- - - -
3028
uint
RWES
[`d;ti]
[ d.ti]
Global
Display Time
Time delay in toggling
between Display Pairs.
0 to 60
0
Instance 1
Map 1 Map 2
- - - -
2356
0x6A (103)
1
0x1D (29)
- - - -
3029
uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this control-
ler's settings to the
selected set.
[SEt1]
User Set 1 (101)
[SEt2]
User Set 2 (102)
[none]
None (61)
None
Instance 1
Map 1 Map 2
26
26
0x(101)
1
0xE (14)
118
1014
uint
RWE
[USr;r]
[USr.r]
Global
User Settings Re-
store
Replace all of this con-
troller's settings with
another set.
[FCty]
Factory (31)
[none]
None (61)
[SEt1]
User Set 1 (101)
[SEt2]
User Set 2 (102)
None
Instance 1
Map 1 Map 2
24
24
0x65
(101)
1
0xD (13)
117
1013
uint
RWE
[CoM]
[`SEt]
Communications Menu
PCoL]
[PCoL]
Communications 1
Protocol
Set the protocol of this
controller to the proto-
col that this network is
using.
[`Std]
Standard Bus (1286)
[Mod]
Modbus RTU (1057)
Modbus
Instance 1
Map 1 Map 2
2492
2972
0x96 (150)
1
7
- - - -
17009 uint
RWE
`Ad;S]
[ Ad.S]
Communications 1
Standard Bus Address
Set the network address
of this controller. Each
device on the network
must have a unique ad-
dress.
The Zone Display on the
front panel will display
this number.
1 to 16
1
Instance 1
Map 1 Map 2
2480
2960
0x96 (150)
1
1
- - - -
17001 uint
RWE
[Ad;M]
[Ad.M]
Communications (1 or 2)
Modbus Address
Set the network address
of this controller. Each
device on the network
must have a unique ad-
dress.
1 to 247
1
Instance 1
Map 1 Map 2
2482
2962
Instance 2
Map 1 Map 2
2500 2980
0x96 (150)
1
2
- - - -
17007 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
*
These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User Set