Function key, Global menu, Function key global menu – Watlow EZ-ZONE PM User Manual
Page 61
![background image](/manuals/359082/61/background.png)
Watlow EZ-ZONE
®
PM Limit Controller
•
58
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`FUn]
[`Set]
Function Key
`leu]
[ LEv]
Function Key (3 to 4)
Active Level
Selects the state in
which the Action Func-
tion will be active.
Pressing the Function
Key will toggle the se-
lected action.
high]
High (37)
[Low]
Low (53)
High
Instance 3
Map 1 Map 2
1360
1600
Instance 4
Map 1 Map 2
1380
1620
0x6E (110)
3 to 4
1
137
10001 uint
RWES
[``Fn]
[ Fn]
Function Key (1 to 2)
Action Function
Program the EZ Key to
trigger an action.
Functions respond to a
level state change or
an edge level change.
Note:
The Limit Reset func-
tion is not available in
firmware revision 11.0
and above.
[none]
None
[LMr]
Limit Reset, edge trig-
gered (82)
[`F;AL]
Force Alarm To Occur,
level triggered (218)
[`AoF]
Control Loops Off and
Alarms to Non-alarm State,
level triggered (220)
[`SiL]
Silence Alarms, edge
triggered (108)
[ALM]
Alarm Reset, edge
triggered (6)
[P;LoC]
Keypad Lockout, level
triggered (217)
[usr;r]
User Set Restore, edge
triggered (227)
None
Instance 1
Map 1 Map 2
1364
1604
Instance 2
Map 1 Map 2
1384
1624
0x6E (110)
1 to 2
3
138
10003 uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Function Instance
Select which instance
the EZ Key will affect.
If only one instance is
available, any selection
will affect it.
1 to 4
0
Instance 1
Map 1 Map 2
1364
1606
Instance 2
Map 1 Map 2
1384
1626
0x96 (110)
1 to 2
4
139
10004
- - - -
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to
use for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
- - - -
0x67 (103)
1
5
110
3005
uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the
applied ac line power
source.
[``50]
50 Hz (3)
[``60]
60 Hz (4)
60 Hz
Instance 1
Map 1 Map 2
886
1006
0x6A (106)
1
4
89
1034
uint
RWES
[C;led]
[C.LEd]
Global
Communications LED
Action
Turns comms LED on or
off for selected comms
ports.
[Con1]
Comm port 1 (1189)
[Con2]
Comm port 2 (1190)
[both]
Comm port 1 and 2
(13)
[`off]
Off (62)
both
Instance 1
Map 1 Map 2
1856
2326
0x6A (103)
1
0x0E (14)
- - - -
3014
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
*
These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E:
EEPROM
S:
User Set