PM Limit Controller

27

Chapter 2 Install and Wire

Warning:

Óç

Use National Electric (NEC) or other

country-specific standard wiring and

safety practices when wiring and

connecting this controller to a power

source and to electrical sensors or

peripheral devices. Failure to do so

may result in damage to equipment

and property, and/or injury or loss

of life.

Note:

Maximum wire size termination and

torque rating:

• 0.0507 to 3.30 mm

2

(30 to 12

AWG) single-wire termination or

two 1.31 mm

2

(16 AWG)

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled

differently, depending on the model

number.

Note:

To prevent damage to the control-

ler, do not connect wires to unused
terminals.

Note:

Maintain electrical isolation be-

tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.

Note:

The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.

EIA-232/485 Modbus RTU Communications

485 common

485 T-/R-

CB
CA
CC
CB
CA

C5
C3
C2

Slot B or E

485 T+/R+

485 T-/R-

485 T+/R+

232 common

232 (TX) to DB9 pin 2 (RD)

232 (RD) to DB9 pin 3 (TX)

• Wire T-/R- to the A termi-

nal of the EIA-485 port.

• Wire T+/R+ to the B

terminal of the EIA-485

port.

• Wire common to the com-

mon terminal of the EIA-

485 port.

• Do not route network

wires with power wires.

Connect network wires in

daisy-chain fashion when

connecting multiple de-

vices in a network.

• A termination resistor

may be required. Place

a 120 Ω resistor across

T+/R+ and T-/R- of last

controller on network.

• Do not wire to both the

EIA-485 and the EIA-232

pins at the same time.

• Two EIA-485 terminals of

T/R are provided to assist

in daisy-chain wiring.

• Do not connect more

than one EZ-ZONE PM

controller on an EIA-232

network.

• Do not connect more than

16 EZ-ZONE PM control-

lers on a Standard Bus

EIA-485 network.

• Do not connect more

than 247 EZ-ZONE

PM

controllers on a Modbus

RTU EIA-485 network.

• maximum EIA-232 net-

work length: 15 meters

(50 feet)

• maximum EIA-485 net-

work length: 1,200 me-

ters (4,000 feet)

• 1/8th unit load on EIA-

485 bus.

PM [4, 6, 8, 9] _ _ _ _-[2]

AAA AAA

Modbus-IDA Terminal

EIA/TIA-485 Name

Watlow Terminal Label

Function

DO

A

CA or CD

T-/R-

D1

B

CB or CE

T+/R+

common

common

CC or CF

common

EtherNet/IP™ and Modbus TCP Communications

receive -

unused

E8
E7
E6
E5
E4
E3
E2
E1

Slot B or E

unused

unused

unused

receive +

transmit -

transmit +

RJ-45

pin

T568B wire

color

Signal

Slot

B or E

8

brown

unused

E8

7

brown & white

unused

E7

6

green

receive -

E6

5

white & blue

unused

E5

4

blue

unused

E4

3

white & green

receive +

E3

2

orange

transmit -

E2

1

white & orange transmit +

E1

EtherNet/IP™ and Modbus TCP communi-
cations to connect with a 10/100 switch.

• Do not route net-

work wires with

power wires.

• Connect one Ether-

net cable per con-

troller to a 10/100

mbps ethernet

switch. Both Modbus

TCP and EtherNet/

IP™ are available

on the network.

• An RUI may be con-

nected at the same

time using Slot C.

PM [4, 6, 8, 9]_ _ _ _

_-[3] _ _ _ AAA

Note:

When changing the fixed IP address cycle module power for new address to

take effect

Ethernet LED Indicators

Viewing the control from the front and then looking on top four LEDs can be

seen aligned vertically front to back. The LEDs are identified accordingly:

closest to the front reflects the Network (Net) Status, Module (Mod) Status is

next, Activity status follows and lastly, the LED closest to the rear of the con-

trol reflects the Link status.

Note:

When using Modbus TCP, the Network Status and Module Status LEDs are

not used.