Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter Name
Description
Range
Default Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`ei;S]
[ Ei.S]
Digital Input (5 to 6)
Event Status
View this event input state.
[`off]
Off (62)
[``on]
On (63)
- - - -
Instance 5
Map 1
Map 2
1408
1648
Offset to next
instance equals
+20
0x6E (110)
5 to 6
5
140
10005 uint
R
No Dis-
play
EZ-Key/s (1 to 2)
Event Status
View this event input state.
[`off]
Off (62)
[``on]
On (63)
- - - -
Instance 1
Map 1
Map 2
1328
1568
Instance 2
Map 1
Map 2
1348
1588
0x6E (110)
3 to 4
5
140
10005 uint
R
[LiM]
[oPEr]
Limit Menu
[`LL;S]
[ LL.S]
Limit (1)
Limit Low Set Point
Set the low process value
that will trigger the limit.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1
Map 2
684
724
0x70 (112)
1
3
38
12003 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1)
Limit High Set Point
Set the high process value
that will trigger the limit.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1
Map 2
686
726
0x70 (112)
1
4
39
12004 float
RWES
[`l;Cr]
[ L.Cr]
Limit (1)
Limit Clear Request
Clear limit once limit con-
dition is cleared.
[`Clr]
Clear (0)
[ignr]
Ignore (204)
0
Instance 1
Map 1
Map 2
680
720
0x70 (112)
1
1
- - - -
12001 uint
W
[`l;st]
[ L.St]
Limit (1)
Limit State
Clear limit once limit con-
dition is cleared.
[`off]
Off (62)
[none]
None (61)
[`li;h]
Limit High
(51)
[`li;l]
Limit Low (52)
[`err]
Error (28)
- - - -
Instance 1
Map 1
Map 2
690
730
0x70 (112)
1
6
- - - -
12006 uint
R
[ALM]
[oPEr]
Alarm Menu
[`A;Lo]
[ A.Lo]
Alarm (1 to 4)
Alarm Low Set Point
If Alarm Type (Setup Page,
Alarm Menu) is set to:
process - set the process
value that will trigger a
low alarm.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
32.0°F
or
units
0.0°C
Instance 1
Map 1 Map 2
1482
1882
Offset to next
instance (Map
1) equals +50
Offset to next
instance (Map
2) equals +60
0x6D (109)
1 to 4
2
18
9002
float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set