Watlow EZ-ZONE

®

PM Limit Controller

43

Chapter 5 Operations Page

Operations Page

Dis-

play

Parameter Name

Description

Range

Default Modbus Rela-

tive Address

CIP

Class

Instance

Attribute

hex (dec)

Pro-

fibus

Index

Param-

eter ID

Data

Type

&

Read/

Write

[`ei;S]
[ Ei.S]

Digital Input (5 to 6)

Event Status

View this event input state.

[`off]

Off (62)

[``on]

On (63)

- - - -

Instance 5

Map 1

Map 2

1408

1648

Offset to next

instance equals

+20

0x6E (110)

5 to 6

5

140

10005 uint

R

No Dis-

play

EZ-Key/s (1 to 2)

Event Status

View this event input state.

[`off]

Off (62)

[``on]

On (63)

- - - -

Instance 1

Map 1

Map 2

1328

1568

Instance 2

Map 1

Map 2

1348

1588

0x6E (110)

3 to 4

5

140

10005 uint

R

[LiM]
[oPEr]
Limit Menu

[`LL;S]
[ LL.S]

Limit (1)

Limit Low Set Point

Set the low process value

that will trigger the limit.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

0.0°F or

units

-18.0°C

Instance 1

Map 1

Map 2

684

724

0x70 (112)

1

3

38

12003 float

RWES

[`Lh;S]
[ Lh.S]

Limit (1)

Limit High Set Point

Set the high process value

that will trigger the limit.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

0.0°F or

units

-18.0°C

Instance 1

Map 1

Map 2

686

726

0x70 (112)

1

4

39

12004 float

RWES

[`l;Cr]

[ L.Cr]

Limit (1)

Limit Clear Request

Clear limit once limit con-

dition is cleared.

[`Clr]

Clear (0)

[ignr]

Ignore (204)

0

Instance 1

Map 1

Map 2

680

720

0x70 (112)

1

1

- - - -

12001 uint

W

[`l;st]

[ L.St]

Limit (1)

Limit State

Clear limit once limit con-

dition is cleared.

[`off]

Off (62)

[none]

None (61)

[`li;h]

Limit High

(51)

[`li;l]

Limit Low (52)

[`err]

Error (28)

- - - -

Instance 1

Map 1

Map 2

690

730

0x70 (112)

1

6

- - - -

12006 uint

R

[ALM]
[oPEr]
Alarm Menu

[`A;Lo]
[ A.Lo]

Alarm (1 to 4)

Alarm Low Set Point

If Alarm Type (Setup Page,

Alarm Menu) is set to:

process - set the process

value that will trigger a

low alarm.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

32.0°F

or

units

0.0°C

Instance 1

Map 1 Map 2

1482

1882

Offset to next

instance (Map

1) equals +50

Offset to next

instance (Map

2) equals +60

0x6D (109)

1 to 4

2

18

9002

float
RWES

Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.

R: Read

W: Write

E: EEPROM

S: User

Set