Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) Algorithms, Tables and Sequential Logic Functions User Manual
Page 93
Logic Functions - Book 2
SUPERVISORY MESSAGE BLOCK
8-85
19
Result Quality (RQ)......................................................................................................... – WR
Indicates the relative quality of the result data.
GOOD
0
If message type is READ, result quality is good if the transaction is
successful. If message type is READ_W_QUAL, result quality is
good if the response quality is good.
BAD
1
If message type is READ, result quality is bad if the transaction failed.
If message type is READ_W_QUAL, the result quality is bad if the
transaction has failed or the response quality is bad.
20
Send Input (SENDINP).......................................................................................................CWR
Logical source pointer to trigger source. Source of signal that triggers the supervisory
message transaction. Signal is edge triggered. Send Input triggers are ignored while the
block is Active.
Trigger
NONE
No Send Input Source; message can only be triggered by an operator write to
the Send Command. If configured as NONE, reading this attribute
will give an invalid attribute error.
LSP
A change in this attribute’s value from 0 to 1 triggers the supervisory message
transaction. Reading this attribute gives the current value of the LSP.
21
Data Input (DATAINP) ........................................................................................................CWR
The data to be transmitted to the source of the “write” message.
NONE
For Read message types only. If configured as NONE, reading this attribute
will give an invalid attribute error.
local value
For Write message types. This value is used in the “write” message.
Reading this attribute gives the constant value.
LSP
For Write message types. Value read from this attribute at trigger time is
used in the “write” message. Reading this attribute gives the current