Logic Functions - Book 2

Totalizer Block

8-101

16

Total Count Quality (TCQ) ................................................................................................. -WR
Quality of Total Count.

GOOD

0

Quality when this block or its controlling loop is RUN or HOLD and
input quality is GOOD if examined (Bad Inputs Rejected).

BAD

1

Quality when this block or its controlling loop is OFF or input quality is
BAD if examined (Bad Inputs Rejected).

17

High Limit Status (HLSTAT)..............................................................................................CWR
The High Limit Status is set FALSE or TRUE as described below. Initial default value is
FALSE.

FALSE

0

This value is FALSE when the UP totalizer is below the high limit.

TRUE

1

Set TRUE when an UP totalizer reaches the high limit. If Auto Wrap is
YES, this value is held TRUE until the next execution of this block,
otherwise it is held TRUE until a reset occurs.

18

High Limit Status Quality (HLSTATQ)............................................................................... -WR
Quality of High Limit Status.

GOOD

0

Quality when this block or its controlling loop is RUN or HOLD and
input quality is GOOD if examined (Bad Inputs Rejected).

BAD

1

Quality when this block or its controlling loop is OFF or input quality is
BAD if examined (Bad Inputs Rejected).

19

Low Limit Status (LLSTAT) ...............................................................................................CWR
The Low Limit Status is set FALSE or TRUE as described below. Initial default value is
FALSE.

FALSE

0

This value is FALSE when the DOWN totalizer is above the low limit.

TRUE

1

Set TRUE when a DOWN totalizer reaches the low limit. If Auto Wrap
is YES, this value is held TRUE until the next execution of this block,
otherwise it is held TRUE until a reset occurs.

20

Low Limit Status Quality (LLSTATQ) ................................................................................ -WR
Quality of Low limit status.

GOOD

0

Quality when this block or its controlling loop is RUN or HOLD and
input quality is GOOD if examined (Bad Inputs Rejected).

BAD

1

Quality when this block or its controlling loop is OFF or input quality is
BAD if examined (Bad Inputs Rejected).

21

Predetermined Count 1 Status (PC1STAT) .....................................................................CWR
Predetermined Count 1 Status - Set TRUE when the totalized count is greater than or equal to
Predetermined Count 1. It is FALSE otherwise. Initial default value is FALSE.

FALSE

0

Totalized count is less than Predetermined Count 1.

TRUE

1

Totalized count is greater than or equal to Predetermined Count 1.