Linearization block parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) Algorithms, Tables and Sequential Logic Functions User Manual
Page 45

Logic Functions - Book 2
LINEARIZATION BLOCK
8-37
8.5.2
Linearization Block Parameters
The mnemonics, valid values and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 8-4. The following further
defines the Linearization Block configuration parameters.
Table 8-4. Linearizer Block Variable Fields, Mnemonics, Byte Counts, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Version
VERSION
1
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
State
STATE
RUN(0), HOLD(1), OFF(2),
DEBUG(3)
CWR Short State
02
Bad Inputs
BADINP
Rejected (0), Accepted (1)
CWR Discrete
03
Diagnostic Group
SUPPGRP
NONE, 1, 2, 3, 4, 5, 6, 7
CWR Long State
04
Calculation error
CERRS
Enable (0), Suppress (1)
CWR Discrete
05
Calc. Error Unacked
CERRU
NO (0), YES (1)
– WR Discrete
06
Calc. Error Unacked Quality
CERRUQ
GOOD (0), BAD (1)
– WR Discrete
07
Calc. Error Active
CERRA
NO (0), YES (1)
– WR Discrete
08
Calc. Error Active Quality
CERRAQ
GOOD (0), BAD (1)
– WR Discrete
09
Initial Result Value
R
Floating Point Value
CWR Floating Pt
10
Result Quality
RQ
GOOD (0), BAD (1)
CWR Discrete
11
Linearization Type
(see description for
long state values)
TYPE
LINEAR; SQUARE;
SQUARE ROOT; MOD
SQUARE; MOD SQRT;
PIECEWISE; INVERSE
PIECEWISE; TC Types B, E,
J, K, N, R, S, T; Inverse TC
Types B', E', J', K', N', R', S',
T';
Platinum,0.003850
Platinum,0.003923
Platinum,0.003902
Platinum,0.003911
Nickel,0.006270
C – R Long State
12
Set quality bad on calculation
error?
SETQBAD
NO (0), YES (1)
CWR Discrete
13
Input
INPUT
Floating Point Value, or LSP
CWR Floating Pt
14
Temperature Scale
SCALE
FAHRENHEIT (0), CELSIUS
(1), KELVIN (3), RANKINE
(2)
CWR Short State
15
Piecewise Table Number
TABLE
Occurrence number of PW
Block
– WR Count
16
Input Range, Bottom
INLO
Floating Point Value
CWR Floating Pt
17
Input Range, Top
INHI
Floating Point Value
CWR Floating Pt
18
Output Range, Bottom
OUTLO
Floating Point Value
CWR Floating
Point
19
Output Range, Top
OUTHI
Floating Point Value
CWR Floating Pt
20