Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) Algorithms, Tables and Sequential Logic Functions User Manual
Page 31
Logic Functions - Book 2
INPUT COMMUNICATION BLOCK
8-23
11
Timeout Diagnostic Active (TOACT)............................................................................... – WR
If the not receiving data diagnostic is enabled, the active status indicates if the diagnostic error
is active even after acknowledgement.
CLEAR
0
Diagnostic error is not active.
ACTIVE
1
Diagnostic error is active.
12
Timeout Diagnostic Active Quality (TOACTQ)............................................................... – WR
If the not receiving data diagnostic is enabled, this status indicates if the quality of the active
diagnostic is GOOD or BAD. Only writeable in DEBUG.
GOOD
0
Quality when the block (or its controlling loop) is RUN or HOLD.
BAD
1
Quality when the block (or its controlling loop) is OFF.
13
Source Diagnostic Counter (SRCCNT)........................................................................... – WR
0-65535. This is a free running count of the source diagnostic errors detected.
14
Source Diagnostic Counter Quality (SRCCNTQ)........................................................... – WR
BAD, GOOD. Indicates the quality of the source diagnostic error counter. Quality is set to
BAD when the block (or its controlling loop) is OFF.
15
Data Update Mode (MODE) ...............................................................................................CWR
Indicates how the data being received is updated. Switching mode is an informational event.
MANUAL
0
In manual the result data and quality are not updated by the source.
The result data is operator writeable in manual. When the block
mode is set to manual from auto, the event message BLOCK MODE
SET TO MANUAL is reported.
AUTO
1
In auto the result data and quality are updated by the source. When
the block mode is set to auto from manual, the event message
BLOCK MODE SET TO AUTO is reported.
16
Initial Data Result (R) ........................................................................................................CWR
This is the block output value after ranging and mode is applied. During startup, this is the
initial data value.
17
Result Quality (RQ)........................................................................................................... – WR
The result quality field depends on how receive quality was configured. The possible
conditions are:
•
Result quality is GOOD when receiving just data.
•
Result quality is the received quality when receive quality is configured as YES.
•
Result quality is BAD when no data is received for two or more seconds.