Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) Algorithms, Tables and Sequential Logic Functions User Manual
Page 92

Logic Functions - Book 2
SUPERVISORY MESSAGE BLOCK
8-84
Locked state
12
Message cannot be accepted because the
destination instrument or LOOP is in the locked
state.
Invalid parameter
14
Message is not accepted because the data value
is out of range for the destination attribute. Or,
the number of bytes sent as data is
unacceptable.
Attribute not writeable
15
Message not accepted because that attribute is
never writeable.
Block not present
17
Message not accepted because the destination
block, although legal, is not present in the
destination instrument.
Invalid mode
18
Message is not accepted due to the present
MODE of the destination BLOCK, LOOP, or
instrument.
Invalid write by configuration
19
Message is not accepted because the
destination attribute is not writeable in its
configuration. Likely reason: an input attribute
that is configured as an LSP.
Instrument state in transition
22
Message not accepted because the destination
instrument is currently changing state and cannot
process the message.
Invalid set-point state
23
Message not accepted because of the
destination block’s current value of
SET_POINT_STATE.
Invalid remote/local status
24
Message not accepted because of the
destination block’s current value of
REMOTE/LOCAL_STATUS.
Invalid message
26
Message not accepted because the message
code is not valid.
In HOLD state
31
Message cannot be accepted because the
destination instrument is currently in the HOLD
state.
18
Initial Data (Result) (R) ......................................................................................................– WR
During startup, this is the initial data value. Initial data, if entered, must be same type as data
type selected. Data sent to the message destination or received in response to a read request
is stored in this field. This field holds the last value sent or received.