beautypg.com

Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) Algorithms, Tables and Sequential Logic Functions User Manual

Page 138

background image

Logic Functions - Book 2

SEQUENCE BLOCK

10-18

14

Calculation Error Active Quality (CERRAQ) ...................................................................– WR
If the calculation error diagnostic is enabled, this status indicates if the quality of the active
diagnostic is GOOD or BAD. Only writeable in DEBUG.

GOOD

0

Quality when the block STATE is RUN or HOLD.

BAD

1

Quality when the block STATE is OFF.

15

Bad Step Error (INVSTS) .................................................................................................. CWR
When a calculated step is out of range or a syntax error is detected in a transition expression
the block reports the diagnostic error as BAD STEP ERROR and takes action in accordance
with the configuration of Attribute No. 43, Bad Step Error Action.

ENABLE

0

Bad step error is enabled

SUPPRESS

1

Bad step error is suppressed

16

Bad Step Error Unacked (INVSTU) ..................................................................................– WR
If the bad step error diagnostic is enabled, the unacknowledged status indicates if the
diagnostic is or is not acknowledged. Only writeable in DEBUG.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

17

Bad step Error Unacked Quality (INVSTUQ) ..................................................................– WR
If the bad step error diagnostic is enabled, this status indicates if the quality of the
unacknowledged diagnostic is GOOD or BAD. Only writeable in DEBUG.

GOOD

0

Quality when the block STATE is RUN or HOLD.

BAD

1

Quality when the block STATE is OFF.

18

Bad Step Error Active (INVSTA) ......................................................................................– WR
If the bad state error diagnostic is enabled, the active status indicates if the diagnostic is active
even after acknowledgement. Only writeable in DEBUG.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

19

Bad Step Error Active Quality (INVSTAQ) .....................................................................– WR
If the bad step error diagnostic is enabled, this status indicates if the quality of the active
diagnostic is GOOD or BAD. Only writeable in DEBUG.

GOOD

0

Quality when the block STATE is RUN or HOLD.

BAD

1

Quality when the block STATE is OFF.

20

Failure Error (FAILS) ......................................................................................................... CWR
When the fail step is executed as a result of a calculation error, bad input error, or a bad step
error the block reports a diagnostic error as FAILURE ERROR to alert the user that the
sequence has been driven to the Fail Step.

ENABLE

0

Failure error is enabled

SUPPRESS

1

Failure error is suppressed