Logic Functions - Book 2

LINEARIZATION BLOCK

8-40

mod sqrt

23 Modified Square Root

Platinum,0.003850

24 Platinum RTD, Alpha 0.003850

Platinum,0.003923

25 Platinum RTD, Alpha 0.003923

Platinum,0.003902

26 Platinum RTD, Alpha 0.003902

Platinum,0.003911

27 Platinum RTD, Alpha 0.003911

Nickel,0.006270

28 Nickel RTD, Alpha 0.006270

13

Set quality bad on calculation error? (SETQBAD) ......................................................... CWR
The result quality can be affected by a calculation error as follows.
NO

0 Result quality is not affected by a calculation error.

YES

1 Quality is set BAD when a calculation error occurs.

14

Input (INPUT) ..................................................................................................................... CWR
The source of the data to be linearized.

value

Fixed initial Floating-Point value for linearizer.

LSP

Floating Point variable is linearization input value.

15

Temperature Scale (SCALE)............................................................................................. CWR
The temperature scale attribute is only used (and is present in the database) when a
thermocouple or RTD type linearization is specified.

FAHRENHEIT 0

Degrees Fahrenheit (C° x 9/5) + 32

CELSIUS

1

Degrees Celsius (F° – 32) x 5/9

RANKINE

2

Degrees Rankine (F°+459.67) or (K° x 9/5)

KELVIN

3

Degrees Kelvin (C°+273.15)

16

Piecewise Table Number (TABLE) ................................................................................... CWR
The occurrence number of the Piecewise Table Block (PW) that is to serve as the linearization
table for this linearization block if the linearization type is piecewise or inverse piecewise. This
attribute is present in the database when piecewise or inverse piecewise is specified.

Input Range Desired? ....................................................................................................... C – –
If the linearization type is linear, square, mod square, square root, or mod sqrt, input ranges
may be configured. The ranges must be configured in pairs. If a range pair is not present, the
default values are 1.0 for high and 0.0 for low.

NO

0

Configured input ranges are not desired. Default values are set. The
input range attributes are not loaded into the database.

YES

1

Configured input ranges is desired. The input range attributes are
loaded into the database and are readable and writeable.

17

Input Range, Bottom (INLO)............................................................................................. CWR
value

Fixed Floating-Point low value of input range for normalization of the
input value.

18

Input Range, Top (INHI) .................................................................................................... CWR
value

Fixed Floating-Point high value of input range for normalization of the
input value.