Logic Functions - Book 2

INPUT COMMUNICATION BLOCK

8-22

05

Receiving unexpected data (SRCSUPP)......................................................................... CWR
Indicates whether the source diagnostic error is enabled or suppressed. This diagnostic is
provided to detect a configuration error (source or data type incorrect) within either this block
or within an Output Communication block in another instrument.

ENABLE

0

The receiving unexpected data (source) diagnostic error is enabled.
When this diagnostic is detected, the diagnostic message
RECEIVING UNEXPECTED MESSAGE is reported.

SUPPRESS

1

The receiving unexpected data (source) diagnostic error is
suppressed. Acknowledgement status remains clear.

06

Unacked Source Diagnostic (SRCUNACK).....................................................................– WR
If the receiving unexpected data diagnostic is enabled, the unacknowledged status indicates if
the diagnostic error is or is not acknowledged.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

07

Unacked Source Diagnostic Quality (SRCUNQ) ............................................................– WR
If the receiving unexpected data diagnostic is enabled, this status indicates if the quality of the
unacknowledged diagnostic is GOOD or BAD. Only writeable in DEBUG.

GOOD

0

Quality when the block (or its controlling loop) is RUN or HOLD.

BAD

1

Quality when the block (or its controlling loop) is OFF.

08

Not receiving data (TOSUPP)........................................................................................... CWR
Indicates whether the timed-out diagnostic error is enabled or suppressed. This diagnostic is
provided to detect a break in the communications that has halted the continual flow of data
from the source. If no new data has been received for 2 seconds, then the timeout diagnostic
is detected.

ENABLE

0

The timed-out diagnostic error is enabled. When this diagnostic is
detected, the result quality is set BAD and the diagnostic message
NOT RECEIVING DATA is reported.

SUPPRESS

1

The timed-out diagnostic error is suppressed. Acknowledgement
status remains clear.

09

Unacked Timeout Diagnostic (TOUNACK)......................................................................– WR
If the not receiving data diagnostic is enabled, the unacknowledged status indicates if the
diagnostic error is or is not acknowledged.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

10

Unacked Timeout Diagnostic Quality (TOUNACKQ) .....................................................– WR
If the not receiving data diagnostic is enabled, this status indicates if the quality of the
unacknowledged diagnostic is GOOD or BAD. Only writeable in DEBUG.

GOOD

0

Quality when the block (or its controlling loop) is RUN or HOLD.

BAD

1

Quality when the block (or its controlling loop) is OFF.