Totalizer Block
8-92
8.10.2
Totalizer Block Timing Diagrams
Totalizer Block Timing Diagram, Figure 8-52, DIRECTION = UP, AUTO WRAP = NO
The totalizer will count up until it reaches the high limit. The high limit status will be set TRUE.
The count will remain at the high limit until a reset occurs at which time the count will be reset
to the low limit. The high limit status will be set to FALSE.
Figure 8-52. Totalizer Block Timing Diagram, DIRECTION = UP, AUTO WRAP = NO
Time
0
30
25
20
15
10
5
35
High Limit Status
Direction = UP, Auto Wrap = NO
Predetermined
Count 1 Status
Predetermined
Count 2 Status
Maximum Count = 9999999.0
Minimum Count = 0.0
Low Limit
High Limit
Predetermined Count 1
Predetermined Count 2
Totalized Count
Run
Reset
Reset
Hold
Stop Run
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE