Logic Functions - Book 2

Totalizer Block

8-92

8.10.2

Totalizer Block Timing Diagrams

Totalizer Block Timing Diagram, Figure 8-52, DIRECTION = UP, AUTO WRAP = NO
The totalizer will count up until it reaches the high limit. The high limit status will be set TRUE.
The count will remain at the high limit until a reset occurs at which time the count will be reset
to the low limit. The high limit status will be set to FALSE.

Figure 8-52. Totalizer Block Timing Diagram, DIRECTION = UP, AUTO WRAP = NO

Time

0

30

25

20

15

10

5

35

High Limit Status

Direction = UP, Auto Wrap = NO

Predetermined
Count 1 Status

Predetermined
Count 2 Status

Maximum Count = 9999999.0

Minimum Count = 0.0

Low Limit

High Limit

Predetermined Count 1

Predetermined Count 2

Totalized Count

Run

Reset

Reset

Hold

Stop Run

TRUE

FALSE

TRUE

FALSE

TRUE

FALSE